169
Smart Power
Outdoor unit dip switch setting
SW1-1 SW1-2 SW1-3 SW1-4 SW1-5 SW1-6 SW1-7 SW1-8 Description
OFF ---- ---- ---- ---- ---- ---- ----
Manually forced operation invalid(default)
ON ---- ---- ---- ---- ---- ---- ----
Manually forced operation valid
---- OFF ---- ---- ---- ---- ---- ----
Manually forced heating(default)
---- ON ---- ---- ---- ---- ---- ----
Manually forced cooling
---- ---- OFF ---- ---- ---- ---- ----
Normal standby cost(default)
---- ---- ON ---- ---- ---- ---- ----
Low stand by power cost
---- ---- ---- OFF ---- ---- ---- ----
Water heater or heating only
---- ---- ---- ON ---- ---- ---- ----
Unit as air conditioner (default)
---- ---- ---- ---- OFF ---- ---- ----
Central control(default)
---- ---- ---- ---- ON ---- ---- ----
BMS
---- ---- ---- ---- ---- OFF ---- ----
Refrigerant R410A(default)
---- ---- ---- ---- ---- ON ---- ----
Refrigerant R32
---- ---- ---- ---- ---- ---- OFF
Defrost automatic(default)
---- ---- ---- ---- ---- ---- ON
Defrost by time
---- ---- ---- ---- ---- ---- ---- OFF
Not for base station
---- ---- ---- ---- ---- ---- ---- ON
Base station application(default)
0151800054B: Dip switch setting Model: 1UH071~140
SW6 (1-ON, 0-OFF)
unit No.(display on the controller)
SW6-8 SW6-7 SW6-6 SW6-5 SW6-4 SW6-3 SW6-2 SW6-1
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 1 1
0 0 0 0 0 0 1 0 2
0 0 0 0 0 0 1 1 3
0 0 0 0 0 1 0 0 4
0 0 0 0 0 1 0 1 5
0 0 0 0 0 1 1 0 6
0 0 0 0 0 1 1 1 7
---- ---- ---- ---- ---- ---- ---- ---- ----
1 1 1 1 1 1 1 1 256
SW8 Denation
0 1UH071N1ERG
1 1UH090N1ERG
2 1UH105N1ERG
4 1UH125P1ERG
5 1UH140P1ERG
8 1UH125P1ERK
9 1UH140P1ERK
Note:
1. If the outdoor unit connects with centralized controller, the unit no.(displayed on controller) = Unit address+1
;
2.The centralized controller includes YCZ-G001,YCZ-A003, YCZ-A004; the max. unit quantity controlled by YCZ-G001 is 32, the
DIP switch setting of SW6-6,SW6-7,SW6-8 must keep all OFF.; for YCZ-A003, it's 128, the DIP switch setting of SW6-8 must
keep OFF; for YCZ-A004 ,it's 256. No DIP switch setting limitation.
3.The protocal slelection in the centralized controller: for YCZ -G001, no need select protocal; for YCZ-A003, the type select in
"Monitor" must be "Unitary"; for YCZ-A004, the "Type Select" in "System Settings" must be "Single".
SW7 (1-ON, 0-OFF)
Denation
SW7-1 SW7-2
0 0 DERD test selection 0
0 1 DERD test selection 1
1 0 DERD test selection 2
1 1 DERD non-test selection