EasyManua.ls Logo

Haier ADH200H1ERG - Page 67

Haier ADH200H1ERG
238 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
65
Smart Power
Item Model ADH160H1ERG/1UH160P1ERG
Function Cooling Heating
Capacity kW 15.5 (3.5~17.5) 18 (6.0~20.0)
Sensible heat ratio 0.74
Total power input kW 4.83 (2.0---7.2) 5.13 (2.0---7.2)
Max. power input W 7200 7200
AEER or ACOP W/W 3.16 3.58
Dehumidifying capacity 10
-3
×m³/h 4.9
Power cable /
Power source N, V, Hz 1ph, 220~240, 50/60
Running/Max.Running current A / A 21(8.7-32)/32A 21.5(8.7-32)/32A
Start current A /
Circuit breaker A
1Ph, 40Afrom outdoor
Indoor unit
Unit model (color) ADH160H1ERG
Fan
Type × Number CENTRIFUGALX2
Speed(H-M-L) r/min
1140/1060/980/900±50r/min(50Pa)
Fan motor input power kW
0.30*2
Fan motor output power kW
0.24*2
Air-ow(H-M-L) m³/h 4000/3400/2800/2200(37Pa-210Pa)
Air-ow(H-M-L) l/s 1100/944/777/611
Heat exchanger
Type/Diameter mm Inner grooved pipe/φ7.0
Total area 0.45
Dimension
External(L×W×H) mm×mm×mm 1350/490/425
Package(L×W×H) mm×mm×mm 1565/724/510
Drainage pipe (material, I.D./O.D.) mm
Controller (O-Optional,S-Standard)
Wired YR-E17(S)
Infrared YR-HBS01(O)
Fresh air hole dimension mm /
Electricity heater kW 0
Sound power noise level (H-M-L) dB(A) 67
Sound pressure noise level (H-M-L) dB(A) 51/47/45/42
Weight (Net / Shipping) kg / kg 61/72
Piping
Refrigerant
Type/Charge g R410A/3700
Recharge quantity g/m 45
Pipe
Liquid mm 9.52
Gas mm 15.88
Between I.D &O.D
MAX.Drop m
30
MAX.Piping length m
75
Norminal condition:
indoor temperature (cooling): 27°C DB/19°C
WB, indoor temperature (heating): 20°C DB
Outdoor temperature (cooling): 35°C DB/24°C WB, outdoor temperature (heating): 7°C DB/6°C WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated