Service diagnosis   
 
 34                   Domestic air conditioner 
 
 
10.3.5 IPM protection 
 
Outdoor display:   □ ★ ★/ F1    LED1  flash  2  times 
 
Method of       
IPM protection is detected by checking the compressor running condition and so on 
Malfunction       
Detection 
 
Malfunction        
■
 
The system leads to IPM protection due to over current
 
Decision 
■
 
The compressor faulty leads to IPM protection 
 
Conditions        
■
 
  circuit component of IPM is broken and led to IPM protection 
 
Supposed 
■
 
  IPM protection dues to the compressor faulty   
Causes 
■
 
IPM protection dues to faulty PCB of IPM module         
■  Compressor wiring disconnected 
 
Troubleshooting    
* Caution   
Be sure to turn off power switch before connect or disconnect connector,      or 
else parts damage may be occurred.   
NO 
YES 
NO 
YES