13
Electric wiring
6.  Test run
CAUTION
THIS UNIT WILL BE STARTED INSTANTLY WITHOUT "ON" OPERATION
WHEN ELECTRIC POWER IS SUPPLIED.BE SURE TO EXECUTE "OFF"
OPERATION BEFORE ELECTRIC POWER IS DISCONNECTED FOR
SERVICING.
This unit has a function of automatic restart system after recovering power stoppage.
Installation Procedure
Failure description
Room temp. sensor abnormal
Indoor coil temp. sensor abnormal
Outdoor coil temp. sensor abnormal/
(compressor discharge temp. sensor)
Over-current malfunction/ power supply abnormal
Communication malfunction between indoor and wired controller
Communication malfunction between indoor and outdoor abnormal
Outdoor coil gas pipe temp. Sensor abnormal
Code on wired  Flash times of indoor
controller          receiver board
01                     Power LED flashes 1 time
02                     Power LED flashes 2 times
4A                     Power LED flashes 3 times
49                     Power LED flashes 4 times
48                     Power LED flashes 5 times
53   Power LED flashes 6 times
07                     Power LED flashes 8 times
06                      Power LED flashes 9 times
03                      Power LED flashes 12 times
Outdoor temp. sensor abnormal
High / Low pressure abnormal
Temperature protection malfunction
0D                      Power LED flashes 13 times
Drainage system malfunction
08                      Power LED flashes 10 times
0B                      Power LED flashes 11 times
Alarm of exterior annunciator
7. Trouble display
(1)  Before starting test run (for all Heat pump models)
Confirm whether the power source breaker (main switch) of the unit has been
turned on for over 12 hrs to energize the crankcase heater in advance of operation.
(2) Test run
Run the unit continuously for about 30 minutes, and check the following.
Suction pressure at check joint of service valve for gas pipe.
Discharge pressure at check joint on the compressor discharge pipe.
Temperature difference between return air and supply air for indoor unit.
The following consults are according to the EMC testing.
Through poor conditions of the electrical MAINS, shortly voltage drops can appear
when starting the EQUIPMENT. This can influence other equipment (eg. Blinking
of a lamp ). But if the Mains-Impedance Zmax value can meet the below chart, such
 disturbances are not expected. (In case of need, you may contact your local supply
authority for further information ).
Model Zmax value
AU60NAIEAA <0.2708OHM
AU48NAIEAA
AU282AHEAA   AU362AIEAA   AU362ALEAA
<0.2984OHM
<0.0741OHM
AU242AGEAA
<0.2721OHM
AU36NAIEAA
<0.2830OHM
<0.2221OHM
AU42NALEAA