electronic expansion valve
AS06
AS06
Combination example:
8 by 1:
NOTE:
1.When AU48 unit is connected with 8 indoor units, pay attention that the total capacity of indoor
units must not exceed 130% of outdoor cooling capacity.
2.Wall-mounted type can not be connected with 8 units by the outdoor unit. But you can refer to
the above combination example.
3.when outdoor unit connects with 6 wall-mounted units and 2 ceiling concealed units, please
set address of wall-mounted type with the address-setting remote controller, and their address
numbers are from 1 to 6, then please set address of ceiling concealed type with dialing
switches, address number 7 and 8.
4.when outdoor unit connects with 8 units according to <admissible combination
example>(except for the No.3 example), please set address of the anterior 6 indoor units with
the address-setting remote controller, and then set address of the latter 2 indoor units with
dialing switches.
Or using below method to set unit 7 and 8: Press button 6 and at the same time in 2
seconds press button 1, then loosen them simultaneously. The LCD will display “7”, which
stands for selecting unit 7. And then press button “set”, you can set unit 7.
By the same method, press button 6 plus button 2, you can set unit 8.