T
echnical Parameters
Correction
1.CA0035EANE
Cooling:
Water outlet
temperature
(
℃)
Ambient temperature (℃)
25
30 35 40 45
kW
5 1.03 0.97 0.94 0.90 0.85
7
1.07 1.03 1.00 0.95 0.88
9
1.10 1.06 1.03 0.98 0.91
11
1.12 1.10 1.08 1.02 0.97
13
1.19 1.20 1.15 1.10 1.05
15
1.31 1.31 1.26 1.20 1.15
H
eating:
Water outlet
temperature
(
℃)
Ambient temperature (℃)
15
10 7 5 0 -5 -10 -15
kW
30
1.23 1.15 1.11 1.06 0.87 0.80 0.71 0.62
35
1.13 1.10 1.08 0.83 0.74 0.68 0.58 0.57
40
1.13 1.09 1.05 0.83 0.74 0.66 0.57 0.55
45
1.13 1.09 1.00 0.83 0.74 0.64 0.57 0.53
50
1.13 1.07 0.92 0.81 0.74 0.64 0.56 0.51
55
1.12 1.06 0.92 0.81 0.72 0.62 - -
2
.CA0070EANE,CA0100EANE,CA0130EANE
Cooling:
Water outlet
temperature
(
℃)
Ambient temperature (℃)
25
30 35 40 45
kW
5
1.07 1.00 0.94 0.94 0.81
7
1.14 1.07 1.00 0.96 0.86
9
1.20 1.13 1.06 0.98 0.91
11
1.27 1.19 1.12 1.04 0.96
13
1.34 1.26 1.17 1.09 1.01
15
1.41 1.32 1.23 1.14 1.06
22
Heating
capacity
Heating
Heating
capacity
Heating
capacity
Heating
Heating
capacity
Heating
Heating
capacity
capacity
capacity
capacity
Cooling
capacity
Cooling
capacity
Cooling
capacity
Cooling
capacity
Cooling
capacity
Cooling
capacity
Cooling
capacity
Cooling
capacity
Cooling
capacity
Cooling
capacity
Factor