7.4.2 Indoor fan motor malfunction
Indoor Display E14
Method of  Malfunction 
Detection
The rotation speed detected by the Hall IC during fan motor 
operation is used to determine abnormal fan motor operation
Malfunction  Decision
Conditions
When the detected rotation feedback singal don’t receiced in 2 minutes
Supposed Causes
Operation halt due to short circuit inside the fan motor winding.
Operation halt due to breaking of wire inside the fan motor.
Operation halt due to breaking of the fan motor lead wires.
Dedection error due to faulty indoor unit PCB.
W hether terminal CN7 and CN13 
on indoor PCB well inserted or not?
Pull out and reinsert  the terminals
Electrify the machine again and turn it on in the 
cooling operation,
 Measure voltage between the  
positions 1 ( 
red wire)
 and 5(
 black wire) of 
Terminal CN7 on the indoor PCB
The voltage is about 90-200vac
   Check whether motor can run when
turn on the unit
When motor is running Measure 
whether  there is voltage pulse(0-5VDC) between 
the
positions 2 (middle 
wire)
 and 3(
 black wire) 
of Terminal CN13 on the indoor 
The indoor pcb is damaged and 
need replace
The indoor motor is damaged and 
need replace
The indoor motor is damaged 
and need replace
The indoor pcb is damaged and need 
replace
YES
YES
YES
YES
NO
NO
NO
NO