4. Heating operation mode.
* temperature control range: 16---30
* temperature difference: ±1
* control feature: the temperature compensation is automatically added and the system will send
the heating signals to the outdoor system.
If TrTs, the outdoor compressor is turned on, the indoor fan will be at the cold air proof
mode.
If Tr>Ts+, the outdoor system is turned off, the indoor fan will be at the heat residue sending
mode.
If Tr<Ts+, the outdoor system will be turned on again, the indoor fan will be at the cold air
proof mode.
*Indoor fan control
manual control: You can choose high, medium, low and automatic speed control.
Automatic: When Tr<Ts, high speed.
When Ts=<Tr=<Ts+2, medium speed.
When Tr> Ts+2, low speed.
When the airflow speed has no delay from the high to low switching, the speed should be delayed
for 3 minutes (remain at high speed for 3 minutes.) before the next switch.
*Airgate location control: the location for the airgate can be set according to your needs.