When the outdoor speed is M or L, the speed will change according to the heat interaction 
temperature. The status will be checked every minute. 
Ta>28℃,high speed 
26℃<Ta<28℃ ,high/ low speed 
Ta<26℃:     Te≧40℃,high speed 
        37℃≦Te<40℃,high/ medium speed 
        35℃≦Te ,medium speed 
        30℃≦Te<35℃,medium/ low speed 
      Te<30℃,low speed 
 
1.4.2  the speed control under the heating mode 
The outdoor speed varies according to the outdoor ambient temperature. M operates on H under 
the two option mode. 
 
 
 
 
 
 
 
 
 
 
 
 
Ta>24℃,low speed 
24℃>Ta>20℃,low speed/ medium speed 
Ta>16℃,medium speed 
16℃>Ta>10℃,medium/high speed 
Ta<10℃,high speed 
 
1.5 Outdoor four direction control 
Under the cooling mode, the outdoor four direction latch is not closed. Under the heating mode, 
the latch can be closed. When the heating compressor stops, the four direction latch will be 
closed 100 seconds later. The latch control under the defrosting operation has been discussed 
in the ‘defrosting operation’. 
 
1.7 compressor frequency control 
1.7.1 fixed test frequency 
To fixing test frequency operation of the outdoor system. 
the indoor system can be controlled manually. (refer to the indoor system specification). 
1.7.1.1 If the indoor system has the fixed frequency test operation function, then the outdoor 
system will calculate the fixed frequency according to the number of the turned on systems 
and operate on the calculated frequency until the indoor system quit the test operation. When 
the two indoor systems are turned on at the same time, the outdoor system will enter the 
operation mode if either of the indoor systems sends the fixed test frequency. 
Ta =24℃ 
Outdoor speed: 
Ta =16℃ 
Ta =10℃ 
Ta =20℃ 
L 
M 
H 
M  L 
Air Conditioner