No.
Phenomenon
The complete machine
does not start without
any reflection after the
power is switched on
The LCD displays, but
the complete machine
can not start.
The refrigerating works
with bad effect
The refrigerating medium is
leaking.
The refrigerating system is
blocked.
The compressor is broken
down.
The air circulation is bad
The fan setting is not
reasonable.
The noise is large.
The indoor temperature sensor
pack is with open circuit
The water tank is full of the
water level seitch is with short
circuit
The water level switch is with
open circuit.
The components are loosen.
The fan is off-center.
The compressor is broken down.
Th machine does not
stop after the water is
full
The sweep fins do not
move or move
abnormally.
The LCD is not
complete or not clear
The LCD foot is with rosin
jiint
The LCD is broken down.
Check the spot weld.
Replace the LCD or major
control board.
The connector of the sweep
motor is loosen.
The spot weld of the sweep
motor is with rosin joint.
Tht swep motor is broken
down.
There's mechanical resistance
with the sweep mechanism.
Repair or replace the connector.
Weld the spot to be under good
condition.
Replace the sweep motor.
Repair or replace the sweep
spindle, pitman, pins.
1
2
3
4
5
6
7
Reason
No power supply or abnormal
power suopply
The fuse is broken
The corrugated copper plate is
burnt
The L end and compressor end
of the compressor relay are
mixed up
The plug between the high
electroplte and the weak
electroplte, or between the
transformer and transformer
and the circuit board is loose.
Check if the power line and plugs
are well
Replace the fuse
Check out the reason of burn-
ing, and welding the copper plate
after debugging
Change the terminals
Insert the plug firmly
Check the circuit of the tempera-
ture sensor pack
Discharge the water or check
the circuit of the water level
switch.
Detect the leakage and fill the
refrigerating medium.
Clean the pipeline system. and
fill again.
Replace the compressor.
Clean the filter screen.
Set reasonable fan speed.
Find out the loosen part and
fasten it
Replace the fan
Replace the compressor.
Check and repair the water level
switch circuit.
`
Remedy
9.2 Trouble shooting 10 SYSTEM FLOW CHART
(1) Refrigerant using:
HM-07C03 uses freon R22 as its refrigerant, when leaving factory, refrigerant
charge is 0.52 g
HM-07C03 R1 uses freon R407C as its refrigerant, when leaving factory,
refrigerant charge is 0.52 g
HM-09CA03 uses freon R22 as its refrigerant, when leaving factory, refrigerant
charge is 0.6 g
HSM-08C03 uses freon R22 as its refrigerant, when leaving factory, refrigerant
charge is 0.75 g
(2) system vacuumize:
After whole set of mobile air conditioner assembling is finished,, use vacuum
pump to draw out air and water in the indoor unit. System vacuum tolerance will
be under 200Pa
(3) Diagram of pipe system:
(4) type of compressor and compressor feature:
1
2
7
1. Evaporator
3. Compressor
5. Connecting pipe
7. Main capillary
2. Gas & liquid separator
4. Fast tie-in
6. Condenser
4
3
4
5
6