Chapter I: Indoor Unit and Main board for Outdoor Unit 
 
Notice: 
During operations under any mode, if short circuit, open circuit and other 
malfunctions of the temperature sensors are detected, the main engine should 
come to a halt immediately. 
1. Outdoor-board: 
1.1.Forced cooling operation switch: 
Short circuit this switch before electrifying, data communication to indoor unit 
will be ignored: 
Forced cooling will function, the 3-minute delay will be cancelled, and the 
following output will be ON simultaneously: 
High wind volume (H) for outdoor fan motor; 
Compressor operates at the frequency of 80Hz. 
1.2.Forced heating operation switch: 
Short circuit this switch before electrifying, data communication to indoor unit 
will be ignored: 
Forced  heating will function, the 3-minute delay will be cancelled, and the 
following output will be ON simultaneously: 
High wind volume (H) for outdoor fan motor; 
Compressor operates at the frequency of 80Hz. 
CPU checks all A/D ports 
B
.
When safeguarding action happens outdoors, the actions in A should be 
OFF, and other inputs are independent of the actions in A. 
C
.
LED output: Goes along even if safeguarding action happens outdoors; 
Cut this switch and go back to the original state. (The out-door safeguarding 
action will continue) 
 
Chapter II: Basic Functions
 
3. Cooling mode 
3.1.The four-way valve does not work (not electrified) 
3.2.The discharge temperature sensor will not be tested within five minutes 
after the compressor is started 
3.3.Outdoor fan motor control: The fan motor starts five seconds after the 
compressor starts, switching conditions for the two gears of wind volume are 
as follows:              T ambient temp. <21
℃
, Low wind volume
                   T ambient temp. >21
℃
, High wind 
volume                  When the fan motor starts up, and 
the ambient temperature is at the return difference (
±
2
℃
), it runs at the low 
wind volume. 
3.4.Compressor control: Frequency range: 30HZ---------120HZ       
             T ambient temp. <16
℃
, the maximum frequency is 
65HZ              16
℃≤
T ambient temp.
≤
30
℃,
the maximum 
frequency is 90HZ 
30
℃≤
T ambient temp.
≤
41
℃,
the maximum frequency is 
110HZ 
 
          T ambient temp.
≥
41
℃,
the maximum frequency is 85HZ 
   Actual temperature and frequency maybe adjusted through EEPROM 
34
 
Model:
HSU-12HS03/R2(DB)
HSU-09HS03/R2(DB)Domestic Air Conditioner