HSU12HG(DB)-SM Wiring Diagrams
26
Domestic Air Conditioner
5.2.5.4 The protection function of AC current:
During the starting process of the compressor, if the AC current is greater than 15A, the frequency of
the compressor decreases at the speed of 1HZ/second.
During the starting process of the compressor, if the AC current is greater than 13A, the frequency of
the compressor decreases at the speed of 0.1HZ/second.
During the starting process of the compressor, if the AC current is greater than 11A, the frequency of
the compressor increases at the prohibited speed.
During the starting process of the compressor, if the AC current is greater than 10A, the frequency of
the compressor increases at the speed of no faster than 0.1HZ/second.
Remarks: when the outdoor temperature is high, there’s compensation for AC current protection.
ŁWhen the outdoor environment temperature is higher than 40ć, AC current protection value
decreases by 10AD
łWhen the outdoor environment temperature is higher than 46ć,AC current protection value
decreases by 15AD
ŃWhen the outdoor environment temperature is higher than 50ć,AC current protection value
decreases by 20AD
5.2.5.5 Antifreezing protection of the indoor heat exchanger
When refrigerating/heating, prevent freezing.
Tpg_indoor Ў is the minimum value of the effective indoor unit (start it and it is in accord with the
running state).
11ć//ice_temp_3+5
ice_temp_3+3 9ć
Increasing slowly
8ć//ice_temp_3+2
Keeping the frequency
ice_temp_3 6ć 6ć
ice_temp_2 5ć Decreasing slowly
ice_temp_1 3ć Decreasing rapidly ice_temp_1
0ć Stop
When Tpg_indoorLJ ice_temp_1ć, the frequency of the compressor decreases at the speed of
1HZ/1second.
When Tpg_indoorLJ ice_temp_2ć, the frequency of the compressor decreases at the speed of
1HZ/10seconds.
When Tpg_indoor begins to rise again, and ice_temp_2İTpg_indoorİ ice_temp_3ć, the frequency
of thecompressor doesn’t change.
When ice_temp_3LJTpg_indoorLJice_temp_3+3ć, the frequency of the compressor increases at the
speed of 1HZ/10seconds.
For example, Tpg_indoorİ0ćˈlast for 2 minutes, and then the outdoor unit will stop, and report
underload malfunction, but don’t send malfunction report to the indoor.
The compressor stops for more than 3 minutes, Tpg_indoor> ice_temp_3+2ć, the compressor
recovers.