EasyManuals Logo

Haier HW-BA101ABT User Manual

Haier HW-BA101ABT
150 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #14 background imageLoading...
Page #14 background image
11
After backlight is lit, hold
and for 5s to check parameter. The parameter value will show in
temperature display area. The indoor unit NO. will be displayed 0 to F ( hexadecimal) at the bottom
right of the parameter value. LED light dot quantity from 1 to 6 matches parameter category from A
to F. Press
to switch indoor unit NO. and switch parameter by or . If untouched for 10s in
parameter checking interface, it will exit automatically or press swing to exit.
The denition of A, b, C, d, E, F is shown as the following table:
Check Parameter
Parameter category Denition Counting method
A Temperature from indoor unit sensor Tai decimal
b Temperature from indoor unit sensor Tc1 decimal
C Temperature from indoor unit sensor Tc2 decimal
d Indoor unit PMV opening/2 hexadecimal
E indoor unit address hexadecimal
F Indoor unit central control address hexadecimal
Operation
After backlight is lit, hold and for 5s to enter into address searching and setting interface.
Communication address will show in temperature display area and indoor unit NO.( 0-F) will display at
the bottom right of parameter. Press
to switch indoor unit NO. When communication address is
blinking, press
or to adjust. Press to conrm changes.
Address searching and setting
The wired controller is able to receive wireless signal. When receiving the correct command, the
buzzer will sound once. When receiving an illegal command, the buzzer will sound three times.
Wireless signal receiving

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Haier HW-BA101ABT and is the answer not in the manual?

Haier HW-BA101ABT Specifications

General IconGeneral
BrandHaier
ModelHW-BA101ABT
CategoryController
LanguageEnglish

Related product manuals