5580 Enterprise Pkwy., Fort Myers, FL 33905 O󰀩ce (239) 694-0089 Fax: (239) 694-0031






NO OIL is shipped in compressor.
Compressor must NEVER be run backwards.

These Safeties ARE Required at Startup to Maintain Hanbell Warranty
a)
Motor Module Trip (INT69HBY): Open for 1 second
b)
Low Oil Level Float Trip: Open for 30-60 seconds
c)
Unsafe Suction: Less than 5 psi for 3 seconds
d)
Low Differential Pressure: Less than 65 psi for 60 seconds (Oil Psi – Suction Psi)
e)
Unsafe Differential Pressure: Less than 35 psi for 5 seconds (Oil Psi – Suction Psi)
f)
Low Discharge Superheat: Less than 25°F for 300 seconds