TROUBLESHOOTING
7
PROBLEM CAUSE SOLUTION
Compressor will not start 1. No power.
2. Breaker off.
3. Thermostat stuck in open
position.
1. Connect power.
2. Turn breaker on.
3. Replace thermostat.
Refrigerator short cycles 1. Differential set too close.
1. Increase differential.
Refrigerator runs continu-
ously
1. Undercharge.
2. Bad thermostat.
3. Dirty condenser.
1. Add refrigerant.
2. Replace thermostat.
3. Clean condenser fins.
Condensation 1. Leak in Gasket.
2. Condensate drain blocked.
1. Reinstall gasket properly.
2. Clean condensate drain.
Temperature too high. 1. Temperature setting too
high
2. Undercharge.
3. Condenser fins blocked.
4. Restricted air flow.
1. Reset temperature
2. Fix charge size.
3. Clean Fins.
4. Ensure air can circulate
around the compressor.
Hot well not heating 1. Breaker OFF.
2. Low water level as indi-
cated by front warning
light.
3. Faulty water level relay.
1. Turn breaker ON.
2. Add water until warning
light is OFF.
3. Replace water level relay.