User's Manual of Fiber Laser Chiller
HL-1000/1500/2000/3000/4000/6000/8000/12000/15000/20000/30000/40000/50000 Series
SCH-/1500/2000/3000 Series
SCL-/1500/2000/3000 Series
SCHYTJ-/1500/2000/3000 Series
SY-1500/2000 Series
User’s Manual of Fiber Laser Chiller
WUHAN HANLI REFRIGERATION TECHNOLOGY CO., LTD.
Add: No. 1, Second Road, XinFuYua, Hannan District, Wuhan, China
Post Code: 430090 Email: hanli-laserchiller@hanlizl.com
Tel: +86-13682641130
www.hanlichiller.com

Questions and Answers

  • L
    Linda OwenAug 18, 2025
    What to do if my HANLI SCH-3000 has compressor overload?
    • M
      melissa68Aug 18, 2025
      If your HANLI Chiller's compressor is experiencing overload, it could be due to a few reasons. The condenser might be dirty and clogged, requiring cleaning. There could be a fluorine leakage, so check for leaks. The air inlet and outlet may be blocked, so clear any debris. Finally, the ring temperature may be too high, so ensure the equipment is in a well-ventilated area.
  • B
    Bryan WiseAug 20, 2025
    What to do if HANLI SCH-3000 displays Compressors Pressure failure?
    • W
      williamsjessicaAug 21, 2025
      If your HANLI Chiller is showing a 'Compressors Pressure failure', there might be several reasons. First, check for poor ventilation and clear any obstructions around the unit. Second, a refrigerant leak could be the cause, so check for leaks. Third, make sure the condensing fan is running; if not, inspect the fan. Fourth, too much dust in the filter can cause this issue, so clean the dust. Lastly, a damaged pressure switch could be the culprit, so check for loose pressure switches and wiring.
  • S
    Scott HannaAug 23, 2025
    Why my HANLI SCH-3000 Chiller displays Room temperature water High temperature alarms?
    • S
      stephanieolsonAug 23, 2025
      If your HANLI Chiller is experiencing Room temperature water High temperature alarms, it could be due to insufficient water flow. Check if there is a return of water at room temperature and if the water circuit is blocked. Another possible cause is poor ventilation, so clear the surrounding clutter.
  • A
    April CarterAug 26, 2025
    What causes Phase sequence alarms on HANLI Chiller?
    • C
      Carl WebsterAug 26, 2025
      If your HANLI Chiller is showing Phase sequence alarms, it could be due to a few reasons. It might be a power supply issue, such as being out of phase. In this case, you should check the power supply. Another cause could be a phase sequence error, which can be resolved by arbitrarily pairing two phase lines. Three-phase unbalance could also trigger this alarm, requiring a check of the power supply circuit. Lastly, a damaged phase sequence protector could be the reason, and in that case, you should replace the phase sequence protector.
  • Q
    qjohnsonAug 28, 2025
    Why is my HANLI SCH-3000 Chiller showing Low temperature water High temperature alarms?
    • K
      Katie MercerAug 28, 2025
      If your HANLI Chiller is experiencing Low temperature water High temperature alarms, it may be due to insufficient water flow, so testing the water supply line is recommended. Poor ventilation could also be the cause, so clear the surrounding clutter. Additionally, too much dust can lead to this problem, so clean the dust from the condenser.
  • R
    robinsonlaurenAug 30, 2025
    What to do if HANLI SCH-3000 Chiller displays Room temperature water Flow alarms?
    • P
      Peter HernandezAug 30, 2025
      If your HANLI Chiller displays Room temperature water Flow alarms, it might be due to a clogged normal temperature water line, so testing the cutting head for backwater is recommended. It could also be due to reversed inlet and outlet connections, so check the inlet and outlet lines. Leakage in the ambient water line can also cause this, so check and tighten water line connections. Finally, a damaged flow switch could be the issue, so replace the flow switch.
  • K
    Kathy AdamsSep 2, 2025
    How to fix Low temperature water Flow alarms on HANLI SCH-3000?
    • M
      Marcus AllenSep 2, 2025
      If you're getting a Low temperature water Flow alarms on your HANLI Chiller, there are a few potential causes. First, the low temperature water line might be blocked, so you should clean the lines. Second, the inlet and outlet connections might be reversed, so check those lines. Third, a leaky suction line could be the problem, so check and tighten the water suction line. Finally, the flow switch might be damaged, so check and replace it if necessary.
  • C
    Catherine LaneSep 5, 2025
    What does Room temperature water Low temperature alarm mean on HANLI SCH-3000 Chiller?
    • R
      Rachel WebbSep 5, 2025
      If your HANLI Chiller displays a 'Room temperature water Low temperature alarm', it indicates that the water temperature of the equipment is low. In this case, check the relay for adhesion.
  • R
    Renee BatesSep 7, 2025
    What does Low temperature water Low temperature alarm mean on HANLI SCH-3000 Chiller?
    • M
      Michael GlassSep 7, 2025
      If your HANLI Chiller displays a 'Low temperature water Low temperature alarm', it indicates that the water temperature of the equipment is low. In this case, check the relay for adhesion.
  • W
    William DurhamSep 9, 2025
    What causes Room temperature water Probe failure in HANLI SCH-3000?
    • R
      Reginald TuckerSep 10, 2025
      If your HANLI Chiller is showing a Room temperature water Probe failure, it could be due to a short circuit or broken wire in the ambient water probe, so inspect the probe terminals and connections. Alternatively, the ambient water probe might be damaged, requiring a replacement probe.

Summary

Maintenance

Dustproof in Summer

Instructions for cleaning dust from the condenser during summer.

Anti-freeze in Winter

Guidance on preventing frost damage during cold weather.

Routine Maintenance

Regular tasks to ensure optimal equipment performance and longevity.

Fault Analysis and Troubleshooting

Warning Notices

General Safety Information

Overview of safety principles, risk levels, and specific operational warnings.

Conditions of Use

Environmental Requirements

Specifies ambient temperature, humidity, and altitude limits.

Medium Requirements

Details acceptable cooling medium types and prohibited substances.

Performance Parameters

Installation

Product Use

LCD Controller Parameter Setting

Winter Frost Protection

Daily Maintenance

HANLI SCH-3000 Series Specifications

General IconGeneral
BrandHANLI
ModelSCH-3000 Series
CategoryChiller
LanguageEnglish