User's Manual of Fiber Laser Chiller
HL-1000/1500/2000/3000/4000/6000/8000/12000/15000/20000/30000/40000/50000 Series
SCH-/1500/2000/3000 Series
SCL-/1500/2000/3000 Series
SCHYTJ-/1500/2000/3000 Series
SY-1500/2000 Series
User’s Manual of Fiber Laser Chiller
WUHAN HANLI REFRIGERATION TECHNOLOGY CO., LTD.
Add: No. 1, Second Road, XinFuYua, Hannan District, Wuhan, China
Post Code: 430090 Email: hanli-laserchiller@hanlizl.com
Tel: +86-13682641130
www.hanlichiller.com

Questions and Answers

  • J
    Jillian FigueroaAug 18, 2025
    What to do if my HANLI SCHYTJ-1500 Chiller has compressor overload?
    • D
      Daniel CoxAug 18, 2025
      If your HANLI Chiller's compressor is experiencing overload, it could be due to a few reasons. The condenser might be dirty and clogged, requiring cleaning. There could be a fluorine leakage, so check for leaks. The air inlet and outlet may be blocked, so clear any debris. Finally, the ring temperature may be too high, so ensure the equipment is in a well-ventilated area.
  • J
    joshua09Aug 20, 2025
    What to do if HANLI SCHYTJ-1500 displays Compressors Pressure failure?
    • D
      Dr. Donald NormanAug 21, 2025
      If your HANLI Chiller is showing a 'Compressors Pressure failure', there might be several reasons. First, check for poor ventilation and clear any obstructions around the unit. Second, a refrigerant leak could be the cause, so check for leaks. Third, make sure the condensing fan is running; if not, inspect the fan. Fourth, too much dust in the filter can cause this issue, so clean the dust. Lastly, a damaged pressure switch could be the culprit, so check for loose pressure switches and wiring.
  • A
    amberriveraAug 23, 2025
    Why my HANLI SCHYTJ-1500 displays Room temperature water High temperature alarms?
    • N
      Natalie JohnsonAug 23, 2025
      If your HANLI Chiller is experiencing Room temperature water High temperature alarms, it could be due to insufficient water flow. Check if there is a return of water at room temperature and if the water circuit is blocked. Another possible cause is poor ventilation, so clear the surrounding clutter.
  • M
    Michael McknightAug 26, 2025
    What causes Phase sequence alarms on HANLI Chiller?
    • B
      Brian RogersAug 26, 2025
      If your HANLI Chiller is showing Phase sequence alarms, it could be due to a few reasons. It might be a power supply issue, such as being out of phase. In this case, you should check the power supply. Another cause could be a phase sequence error, which can be resolved by arbitrarily pairing two phase lines. Three-phase unbalance could also trigger this alarm, requiring a check of the power supply circuit. Lastly, a damaged phase sequence protector could be the reason, and in that case, you should replace the phase sequence protector.
  • H
    hharringtonAug 28, 2025
    Why is my HANLI Chiller showing Low temperature water High temperature alarms?
    • T
      Tara NielsenAug 28, 2025
      If your HANLI Chiller is experiencing Low temperature water High temperature alarms, it may be due to insufficient water flow, so testing the water supply line is recommended. Poor ventilation could also be the cause, so clear the surrounding clutter. Additionally, too much dust can lead to this problem, so clean the dust from the condenser.
  • M
    Megan ReedAug 30, 2025
    What to do if HANLI Chiller displays Room temperature water Flow alarms?
    • C
      Christopher WangAug 30, 2025
      If your HANLI Chiller displays Room temperature water Flow alarms, it might be due to a clogged normal temperature water line, so testing the cutting head for backwater is recommended. It could also be due to reversed inlet and outlet connections, so check the inlet and outlet lines. Leakage in the ambient water line can also cause this, so check and tighten water line connections. Finally, a damaged flow switch could be the issue, so replace the flow switch.
  • C
    ctaylorSep 2, 2025
    How to fix Low temperature water Flow alarms on HANLI Chiller?
    • J
      Joanne HooperSep 2, 2025
      If you're getting a Low temperature water Flow alarms on your HANLI Chiller, there are a few potential causes. First, the low temperature water line might be blocked, so you should clean the lines. Second, the inlet and outlet connections might be reversed, so check those lines. Third, a leaky suction line could be the problem, so check and tighten the water suction line. Finally, the flow switch might be damaged, so check and replace it if necessary.
  • K
    Kristen OchoaSep 4, 2025
    What does Room temperature water Low temperature alarm mean on HANLI SCHYTJ-1500 Chiller?
    • C
      Christopher CortezSep 4, 2025
      If your HANLI Chiller displays a 'Room temperature water Low temperature alarm', it indicates that the water temperature of the equipment is low. In this case, check the relay for adhesion.
  • R
    rileyalexSep 7, 2025
    What does Low temperature water Low temperature alarm mean on HANLI SCHYTJ-1500 Chiller?
    • T
      Tamara BrownSep 7, 2025
      If your HANLI Chiller displays a 'Low temperature water Low temperature alarm', it indicates that the water temperature of the equipment is low. In this case, check the relay for adhesion.
  • E
    Emily AndrewsSep 9, 2025
    What causes Room temperature water Probe failure in HANLI SCHYTJ-1500 Chiller?
    • J
      Joel GeorgeSep 9, 2025
      If your HANLI Chiller is showing a Room temperature water Probe failure, it could be due to a short circuit or broken wire in the ambient water probe, so inspect the probe terminals and connections. Alternatively, the ambient water probe might be damaged, requiring a replacement probe.

Summary

General Safety Warnings

Safety Precautions for Professional Personnel

Ensures operations are performed by qualified professionals to prevent injury.

High Voltage and Scald Risk Warnings

Identifies risks associated with high voltage and hot surfaces.

Electrical Connection Safety

Details requirements for power supply, cables, and grounding.

Maintenance and Scrap Safety

Outlines safe practices for maintenance and equipment disposal.

Operational Restrictions

Specifies limits on usage, environment, and component integrity.

Transport and Installation Safety

Ensures secure equipment handling during transport and installation.

Operational Fault and Refrigerant Safety

Addresses hazards from abnormal operation and refrigerant leaks.

Handling and Environmental Guidelines

Covers proper handling, tilt limits, and environmental installation constraints.

Operational Checks and Maintenance Safety

Lists pre-operation checks and safety during maintenance.

Operating Conditions

Installation Guidelines

Installation Conditions and Requirements

Checks upon unpacking and requirements for stable, safe installation.

Equipment Installation Form Requirements

Illustrates correct and incorrect equipment installation forms.

Installation Space Requirements

Specifies clearance needed for air suction and exhaust for proper heat dissipation.

Waterway Connection Procedures

Electrical Circuit Connection

Adding Water and Air Exhaust

Product Operation and Commissioning

Parameter Setting Procedures

Routine Maintenance

Fault Analysis and Troubleshooting

Fault Codes and Descriptions

Lists fault codes (E01-E07), failure analysis, movement, and exclusion methods.

Fault Codes and Troubleshooting (Continued)

Details faults E08-E12, probe/flow issues, and LCD controller faults.

LCD Controller Fault Names and Reset

Lists LCD controller faults, testing conditions, troubleshooting, and reset methods.

LCD Controller Faults and Reset Procedures

Covers probe, water flow switch, and water level switch alarms and their resets.