12 
Do  not  burn  any  fuel  other  than  wood,  such  as 
charcoal, which can cause increased carbon monoxide 
production  or  overfiring.  Never  use  highly  volatile 
substances in your stove, such as gasoline, which could 
cause an explosion.
When solid fuels are burned completely, they produce 
water  and  carbon  dioxide.  However,  in  long  slow 
burns, a substantial amount of carbon monoxide may 
be produced.  If allowed to build up, carbon monoxide 
(which is odorless) can prove fatally poisonous. Proper 
ventilation and draft will prevent this from happening. If 
you smell smoke, turn up the air control lever setting, 
and  thoroughly  ventilate  your  dwelling.  During  future 
burns, be careful not to overload the stove with fuel, so 
you will not be tempted to constantly operate at a low 
air control setting.
Other  causes  of  poor  ventilation  or  draft  are  icing, 
exhaust  fans,  a  blocked  outside  air  inlet,  and  room 
air  starvation.    If  your  stove  is  sluggish  and  you  get 
occasional odor, check these possibilities and increase 
the air ow in your home.
When  venting  your  TL300  using  a  prefabricated 
chimney,  be  sure  to  contact  local  building  code 
authorities,  and  to  follow  the  manufacturer’s 
instructions  exactly.  Use  only  the  manufacturer’s 
parts; do not use makeshift installation techniques.  All 
prefabricated  chimneys  must  be  tested  to  either  the 
U.S. or Canadian high-temperature standards, UL 103 
or ULC S629.
If you plan on using a pre-existing masonry chimney, 
have it  thoroughly inspected  and  cleaned. Any faults 
which make the chimney unsafe and unusable must be 
repaired prior to use. These can include improper height, 
structural defects, blockages, inadequate clearance to 
combustibles, unsealed openings into other rooms of 
the house, signs of creosote or smoke leakage, a loose 
or absent clean-out door, or absence of a liner.
When  connecting  to  a  masonry  chimney,  several 
provisions  are  standard.    First,  whether  the  chimney 
connector is vented to the chimney through a thimble 
or a breech pipe, neither must pass beyond the inner 
surface of the chimney liner, and both must be rmly 
cemented in place with refractory cement. (A thimble is 
a masonry pipe which is inserted through the chimney 
wall, and is frequently the preferred method; a breech 
pipe is  a  piece of  steel  pipe  used  the  same  way.)  In 
Canada, a breech pipe has ridges or protrusions to lock 
it rmly into the refractory cement. In either case, the 
chimney connector vents to the chimney through the 
thimble or breech pipe.
Using  a  thimble,  the  connector  slides  completely 
inside the masonry to the inner edge of the ue liner, 
and may be easily removed for chimney and connector 
inspection. A breech pipe must extend at least 2" (50 
mm) into the room, so the connector can be attached 
with sheetmetal screws.
In some situations, a code compliant chimney origi-
nally used for a masonry replace may be used to install 
your TL300. In  addition  to the  requirements  found in 
the  previous  paragraphs,  it  is  important  to  be  aware 
that all clearances must be met, including those from 
the chimney connector to combustibles.  Do not forget 
to include oor protection in your plans.  (See Clear-
ances and Floor Protection in this section.)  Since many 
replaces have exposed wooden mantels and trim, pay 
special attention to the clearances necessary to these 
materials.
If your replace chimney is behind a combustible wall, 
you must use an approved wall pass-through system 
to gain access to the masonry chimney. The chimney 
connector must enter the chimney at a place where it 
is  lined,  and  the  replace  must  be  made  inoperable. 
For example, you might remove the damper, replacing 
it with a secure, airtight, noncombustible seal (remov-
able for inspection); this also satises the requirement 
that no room air must be allowed to enter the chimney.