Questions and Answers

  • T
    Timothy RamosSep 9, 2025
    What to do if Hedy HD700-40T00400 experiences User +24V supply overload?
    • K
      Kathleen GreenSep 9, 2025
      If your Hedy Controller shows a User +24V supply overload, check if there is a short circuit on the output of +24V, DO1 or DO2.
  • T
    Tammy CherryAug 23, 2025
    What to do if Hedy HD700-40T00400 Controller auto-tune failed?
    • M
      martinezjenniferAug 23, 2025
      If the auto-tune process fails on your Hedy Controller, there could be a few reasons. First, the drive size might not match the motor power size; if this is the case, change the drive to the correct rating. Second, the wrong motor data might have been set, so enter the correct motor nameplate data into the drive. Finally, the user might have attempted to stop the drive before the auto-tune finished. Try to autotune again, and do not attempt to stop the drive when the autotune is taking place.
  • J
    johnandrewsAug 25, 2025
    What causes Hedy HD700-40T00400 current limit to be active?
    • T
      tonyknightAug 25, 2025
      The current limit being active on your Hedy Controller can stem from a few issues. It may be because the output current has reached the value set in P07.03 (current limit), possibly due to the drive trying to accelerate the load faster than it is able with the value set in P07.03. If the actual acceleration rate achieved in the application is acceptable then there is no need to adjust parameters. If faster acceleration is required with the maximum value set in P07.03 then a larger motor and drive may be needed. Another cause may be an excessive load on the motor, so check the load. Also, the motor might be spinning on start, so check P03.05 (start mode) is set correctly.
  • M
    Martin JohnsonAug 27, 2025
    What to do if Hedy Controller has output motor terminal short circuit at power up?
    • B
      Benjamin ReyesAug 27, 2025
      If your Hedy Controller shows an output motor terminal short circuit at power up, it's likely due to a short circuit in the output motor terminal. You should check the motor wiring and motor insulation.
  • P
    Phillip MartinezAug 27, 2025
    What to do if Hedy HD700-40T00400 indicates EEPROM read & write failure?
    • K
      Kimberly TurnerAug 27, 2025
      If your Hedy Controller displays an EEPROM read & write failure, it means an error occurred when reading or writing the control word. Press the STOP key to reset the drive and try again.
  • K
    Katie WalkerSep 23, 2025
    What to do if Hedy HD700-40T00400 has Drive software issue?
    • R
      renee76Sep 23, 2025
      If your Hedy Controller has a drive software issue, it indicates an MCU or DSP failure. Contact the supplier of the drive.
  • D
    Donald BakerSep 16, 2025
    What to do if Hedy HD700-40T00400 has Over current during power up?
    • R
      Robert ClarkSep 16, 2025
      If your Hedy Controller shows an over current during power up, it indicates a current sense circuit failure. Contact the supplier of the drive.
  • J
    John HamiltonSep 18, 2025
    What to do if Hedy HD700-40T00400 Controller has IGBT thermistor failure?
    • R
      Ricky StewartSep 18, 2025
      If your Hedy Controller displays an IGBT thermistor failure, it means there is an IGBT failure. Contact the supplier of the drive.
  • L
    Lisa NealSep 7, 2025
    What to do if Hedy Controller MCU receives wrong data from DSP?
    • B
      Barbara TaylorSep 7, 2025
      If the MCU receives wrong data from DSP in your Hedy Controller, it could be due to external disturbance, so check cable layout. It could also be an internal drive fault, in which case you should contact the supplier of the drive.
  • S
    Steven RogersSep 4, 2025
    What to do if Hedy HD700-40T00400 Controller control fan fault (30kW and above)?
    • C
      carpenterrobinSep 4, 2025
      If you're experiencing a control fan fault (30kW and above) with your Hedy Controller, check the fan blades because the fan blade might not be rotating correctly.

Summary

Safety Information

Safety Symbols

Explains danger and warning symbols and associated hazards.

Installation

Drive Clearances

Electrical Installation

Power Connection Guidelines

Typical Power Connections

Illustrates standard wiring diagrams for power connections.

Recommended Fuses and Cables

Provides recommendations for fuses, MCBs, and cable sizing.

Control Connections

Control Terminal Specifications

Using the Keypad

Changing Parameters

Quick Commissioning

Keypad Control Commissioning

Guides on getting the motor running using the keypad control.

Terminal Control Commissioning

Terminal Control Commissioning

Guides on getting the motor running using terminal control.

Fixed Speed Commissioning

Fixed Speed Commissioning

Steps to commission the drive for fixed speed operation.

P00 Parameters

P00 Parameter Descriptions

Troubleshooting

Faults and Corrective Actions

Lists trip codes, descriptions, possible reasons, and corrective actions.

Alarms

Drive Alarms

Explains alarm codes, their possibilities, and recommended treatments.