HE 5731 Operating instructions
The LED flashes.
The display shows the
relevant valve
The permissible valve current
of 1 A has been exceeded
Check the indicate valve
for short-circuit
Check the valve in
question
Check if the valve plug
is connected correctly.
Display is dark or lights
up briefly and goes out
again immediately
The internal fuse triggers (Af-
ter a recovery time of a few
minutes, the controller can
be switched on again)
Switch off the operating
unit
Check whether the am-
bient temperature is
above the permissible
Check current consump-
tion of solenoid valves
Observe restrictions.
The segment display
flashes. In the first field
a „d“ is indicated
The pressure switch (as an
option) indicates a misfunc-
tion at the displayed valve or
at the pressure switch itself.
Check valve / pressure
switch
Red LED is lit on the
valve extension
A wrong knot number has
been set.
Check set knot number
and adjust if necessary