INSTALLATION, MAINTENANCE AND USER'S GUIDE
FAN WITH ELECTRONICALLY COMMUTATED EXTERNAL-ROTOR MOTOR
Fan Code:
0318-4-1005
Fan type : R18R-080MPS-ET120B-01A01
&
Note :
Table of Contents :
01
SAFETY
02
TYPICAL FEATURES AND PROPER USE
03
OPERATING CONDITIONS
04
INSTALLATION AND CONNECTION
05
SPEED CONTROL
06
PUTTING INTO OPERATION
07 DIAGNOSTICS & TROUBLESHOOTING
08
PROTECTIVE FEATURES
09
MAINTENANCE, SERVICE AND CLEANING
10
TRANSPORT AND STORAGE
11
ErP, ROHS AND EMC DIRECTIVES
12
SERVICE ADDRESSES AND ADDITIONAL DATA
This document contains instructions and information for the operation, installation, connection, use and maintenance of
the product. Be sure to familiarize yourself with these instructions before working on this unit. Not paying attention to
these warnings and instructions may lead to malfunctions and failures or may seriously endanger human life. More
detailed information and instructions are available from the manufacturer on request.
Symbols :
WARNING - to indicate warning situation
WARNING - to indicate hot surfaces
DANGER due to electric shock
NOTE - indicate valuable information
Question and Answer IconNeed help?

Do you have a question about the HIDRIA R18R-080MPS-ET120B-01A01 and is the answer not in the manual?

Summary

Safety Guidelines

General Safety Guidelines

Essential safety instructions for handling, installation, operation, and environmental conditions.

Electrical and Personal Hazards

Warns about electrical dangers, rotating parts, hot surfaces, and protective measures for personnel.

Proper Use and Typical Features

Use Restrictions

Outlines limitations and specific applications for the fan's intended use.

Product Features

Details key features like variable speed, efficiency, and integrated filter.

Operating Conditions

Operational Parameters

Specifies conditions for continuous operation, cycling, and environmental limits.

Dimensions and Weight

Provides physical dimensions and the weight of the fan unit.

Nominal Data and Label Explanation

Explains nominal technical data and the content of the product label.

Installation and Connection

Mechanical Installation

Instructions for physically mounting the fan, ensuring stability and air gaps.

Electrical Installation

Guidelines for electrical connection, protection, and disconnection means.

Connecting Diagram and Power Supply

Details the wiring diagram, power supply, and control circuit connections.

Speed Control

Speed Control Methods

Explains control methods like linear voltage, current, and PWM signals.

Linear Voltage Input Control

Details the linear voltage input for speed control, including modes and hysteresis.

Input Characteristic Adjustment

Describes how to adjust the input characteristic for optimal system performance.

Protective Features

Motor and Electronic Protection

Details protection mechanisms against short circuits, locked rotors, and voltage variations.

Putting into Operation

Pre-operation Checks

Lists essential checks like installation, electrical connection, and impeller rotation.

Initial Start-up

Instructions for switching on the power supply and control signal to start the fan.

Diagnostics and Troubleshooting

Fan Start-up and Operation Issues

Addresses issues like fan not starting, running at half speed, and their causes.

Alarm Relay Diagnostics

Explains when the alarm relay is activated and its contact capabilities.

Multi-Colour LED Diagnostics

Details the meaning of green, orange, and red LED statuses for troubleshooting.

Maintenance, Service and Cleaning

Maintenance and Service Precautions

Safety rules for maintenance and service, emphasizing qualified personnel and power disconnection.

Cleaning Procedures

Guidelines for cleaning the fan, including what to avoid and how to clean safely.

Transport and Storage

Transport Guidelines

Instructions for transporting the fan, including packaging and handling.

Storage Recommendations

Advice on storing the fan in a dry area, temperature limits, and shelf life.

ErP, RoHS and EMC Directives

Mounting for Efficiency

Suggestions for fan mounting to achieve optimal efficiency and lifespan.

Environmental Compliance

Information on environmental compliance with RoHS and REACH directives.

Service Addresses and Additional Data

Support and Specifications

Directs users to the website for subsidiary lists and notes on specification changes.

Overview

This document outlines the installation, maintenance, and user guide for a Hidria fan with an electronically commutated external-rotor motor, specifically model 0318-4-1005 (type R18R-080MPS-ET120B-01A01).

Function Description

The Hidria fan is designed as a built-in component for air-conditioning, air supply, and air extraction systems. It is intended for the transfer of air or air-like mixtures and should not be used in hazardous areas for gas, mix vapors, or mixtures, nor for transferring solid components. The fan operates as a variable speed device, with speed control via linear voltage input (0-10V), PWM signal, or other common methods. It features high efficiency and low-noise operation across its entire speed range. The control circuit is SELV isolated from the main power supply, including an external power supply for sensors. The fan is equipped with an integrated EMC filter and maintenance-free ball-bearings, and its rotating parts are dynamically balanced. It is designed for continuous operation (S1 according to IEC 60034-1) and is compatible with the Modbus RTU protocol.

Important Technical Specifications

  • Fan Code: 0318-4-1005
  • Fan Type: R18R-080MPS-ET120B-01A01
  • Nominal Diameter: 800 mm
  • Weight: 50 kg
  • Phase: 3~
  • Nominal Voltage: 400 V
  • Operating Voltage Range: 380-480 V
  • Frequency: 50 Hz
  • Input Power: 2900 W
  • Nominal Current: 4.6 A
  • Rotational Speed: 1140 RPM
  • Operating Ambient Temperature Range: -25°C to +65°C (limited to +60°C if the end-use requires compliance with IEC/EN 60335 standards due to cable temperature limitations; use PVC 105°C cables above 60°C).
  • Altitude: 2000 m
  • Insulation Class: 155
  • Protection Provided by PE: Class I
  • Overvoltage Category (OVC): III
  • Operating Humidity Ambient: Up to 95% (non-condensing)
  • Max. Pressure: 260 Pa
  • Protection (Motor & Electronics): IP55 according to EN60529
  • Power Consumption in Stand-by Mode: Less than 5W
  • Overall Efficiency (ErP): Effes: 47.8%
  • Installation Category (ErP): A
  • Efficiency Category (ErP): Static
  • Efficiency Grade (ErP): N: 51.4
  • Variable Speed Drive (ErP): Integrated
  • Power Input (ErP): Pelec: 2708.1 W
  • Airflow Volume (ErP): qV: 18519 m³/h
  • Pressure Increase (ErP): ps: 250 Pa
  • Rotational Speed (ErP): n: 1146 RPM
  • Specific Ratio (ErP): 1.002
  • Airflow Volume Max. (ErP): qV: 27336 m³/h
  • Pressure Increase Max. (ErP): ps: 610 Pa
  • Sensor Power Supply: 10VDC, max. 10mA
  • Alarm Relay Contacts Capability: max. 2A-250VAC cos fi0.6, max. 3A-30VDC
  • Short Circuit Rating: <10kA
  • Recommended Power Supply Cable: Heat resistant PVC or other cable of appropriate quality (105°C) acc. to IEC 60227-5, e.g., H05V2V2-F, 4G 1.5 mm² (min.1.0 mm² - max. 2.5 mm² for stranded leads or max. 2.5mm² for solid conductors), outer diameter 6.0 - 11mm.
  • Recommended Alarm Circuit Cable: Ordinary PVC cable acc. to IEC 60227-5, e.g., H05V2V2-F, 2X 1 mm² (min.2X 0.50mm² - max. 2X 1.5mm²), outer diameter 5.0 - 9.5mm.
  • Recommended Control Circuit Cable: Ordinary PVC cable, e.g., H05VV-F, 5X 0.5 mm² (min. 0.25 mm² - max. 0.75 mm²), no longer than 2m, outer diameter 6.0 - 11mm.

Usage Features

  • Installation: The fan must be installed by qualified personnel, gripping the motor housing gently to avoid shocks. Safety shoes and cut-resistant gloves are recommended. It is primarily constructed for installation with the rotor on the bottom or with the shaft in a horizontal position. The fan must be fixed to a stationary housing using 8x M8 screws through holes on a diameter of 816 mm of the protection grid, with property class 8.8 screws and secured with Loctite or self-locking screws. A minimum 3 mm air-gap between the fan impeller and stationary housing is crucial. Lifting devices should be used with the provided hangers for safe handling.
  • Electrical Connection: Main electrical installation must be protected against short circuits (e.g., circuit breaker: max.16A, 400Vac, Type B). Means for disconnection must be incorporated in the fixed wiring. An all-pole separating switch must disconnect the fan. If a residual current-operated protective device (RCD) or monitoring (RCM) device is used, only a Type B+ RCD or RCM is allowed on the supply side, with a recommended sensitivity of 300mA and short time delayed intervention. The electrical connection must follow the enclosed connection diagram. Cable sheath needs to be stripped 50-60mm, and stranded wire ends should have insulated ferrules (pin length 8-10mm). The fan uses push-in spring terminals (PHOENIX SPTA or equivalent). A screwdriver of 0.6X3.5mm is needed for mains terminals, and 2.5x0.5mm for control circuit terminals. The terminal box screws should be tightened to 2.0Nm - 2.5Nm.
  • Operation: The fan is designed for continuous operation. Extreme ON-OFF switching should be avoided. Cycling operating mode should only be via control signal (0/10V analog input or PWM input), not by cycling the power supply. The fan should not be operated in an explosive atmosphere.
  • Speed Control: Speed can be controlled by linear voltage input (0-10V), current input (4-20mA), or PWM input (PWM duty cycle 0-100%). A hysteresis of approximately 200mV is implemented to prevent rapid cycling between standby and run modes. The input characteristic can be factory-adjusted for sensitivity or attenuation.
  • Protective Features:
    • Short-circuit protection: Motor and electronic controller are protected by a built-in fuse.
    • Locked-rotor protection: The motor switches off electronically if the rotor is blocked and restarts automatically after de-blocking.
    • Mains under voltage: The motor runs with degraded performance if mains voltage falls below nominal, switching off electronically below 320V and restarting automatically when voltage returns to normal.
    • Over temperature protection: An internally connected thermal protector protects electronics and motor.
  • NFC/RFID Wireless Communication: The fan has an integrated NFC/RFID tag (ISO/IEC 15693) for advanced custom functionality configuration. The aluminum cover must be removed to access the tag.
  • Diagnostics & Troubleshooting:
    • Alarm Relay Diagnostics: Alarm relay contact OPEN on ERROR conditions (rotor locked >10s, motor winding overheating, power module overheating, DC link undervoltage, internal communication error). The alarm relay becomes operable 3-4 seconds after switching on line voltage, changing to CLOSE if no malfunction is detected.
    • Multi-Colour LED Diagnostics:
      • GREEN STATUS: No malfunction detected.
      • ORANGE STATUS: Missing control signal (if 'Emergency operation' is active), electronics/motor/power module high temperature, or break active.
      • RED STATUS: Rotor locked, motor overheating, power module overheating, DC link undervoltage error, or internal communication error.
    • If fan failure (short/open in electronics/windings) is detected, do not attempt to repair; replace the fan or return it to the manufacturer.

Maintenance Features

  • General Maintenance: Before any maintenance or repair, the unit must be securely disconnected from all power supply sources. Only qualified and authorized personnel should open, maintain, or repair the unit.
  • Cleaning: Regular inspection and cleaning are necessary to prevent imbalance from dirt buildup. Blades must be cleaned carefully to avoid damage. Never use high-pressure cleaners or water sprays. Wet cleaning under voltage can lead to electric shock. Do not use aggressive paint solvent cleaning agents; use a moist cloth. If water penetrates the motor, windings must dry before restarting. Cleaning and user maintenance should not be done by children without supervision.
  • Storage: Store fans in original packaging in a dry, weather-protected area, away from extreme heat and cold. A maximum of one year of storage is recommended. Inspect bearings for proper operation after long storage periods.
  • Transport: Transport units only in their original packaging. When transporting fans with wood spacers on pallets, be careful with cables. When unpacking, grip the fan to the protection grill, avoiding force on cables. When transporting fans mounted on final units, ensure they are properly secured and do not touch other devices.
  • Long-term Shutdown: If an installed fan is switched OFF for a long period in a humid atmosphere, it should be switched ON for a minimum of two hours every month to remove condensed moisture inside the motor.
  • Environmental Compliance: The fan uses environment-friendly, recyclable materials according to RoHS2 (2011/65/EU) and REACH (EC1907/2006). Disposal must be professional and environmentally friendly, complying with local regulations. The product design allows for simple decomposition of components, which are marked for easy handling at end-of-life.
  • EMC Compliance: Compliance with EMC standards must be established on the final appliance, as mounting situations can affect EMC properties.

HIDRIA R18R-080MPS-ET120B-01A01 Specifications

General IconGeneral
BrandHIDRIA
ModelR18R-080MPS-ET120B-01A01
CategoryFan
LanguageEnglish