Page #1 background imageLoading...
Page #1 background image
HI LO 1
Line Module
S
S S S
HI LO S HI LO S HI LO S HI LO S
XA1
XA2
XA3
XA4
XA5
XA6
XA7
XA8
TM
Setup
AEB8 Quick Installation
Expansion Board Interface
Cable Connector
(EBIC3 or EBIC5)
Address Jumpers
stranded, shielded
twisted pair
Alarm Input Connectors
(XA1 - XA4)
Alarm Input Connectors
(XA5 - XA8)
No more than 2 AEB8s can be installed in the M2, M8, M64, MSP-8R, or MSP-64R.
The M16 cannot accommodate an AEB8.
There are two jumper positions in the middle of the board which control board
addressing:
Jumper Addresses
J1 1 - 8 (factory default for first AEB8)
J2 9 - 16 (default for second AEB8)
TM
1900 Carnegie Ave. Bldg. B
Santa Ana, CA 92705-5520
(949) 250-8888
www.hirschelectronics.com
rev. 10/00
Testing
After installing the board, you can test it by following this procedure:
1. Attach a printer to the Controller or make sure the Controller is attached to a
SCRAMBLE*NET PC.
2. Power the system up by first connecting the AC power, then the standby
battery.
3. The system goes through its self-test. You should see this information printed
out at the local printer.
Under the Configurations section, you should see this:
Expansion Inputs = 8
if one AEB8 is installed and
Expansion Inputs = 16
if two AEB8s are installed.
Under the Options section, you should see this line:
AEB8-1
if one AEB8 is installed and
AEB8-2
if two AEB8s are installed.
4. Use Command 88*2 from the ScramblePad to request the Max Users and
Options information, or use Host PC software.
5. If the correct information doesn’t appear on the printouts, power down the
Controller and recheck the EBIC connections, then retry the test procedure. If
it still doesn’t work, contact Hirsch.
The AEB8 is an 8-input Alarm Expansion board where each input is supervised like the
inputs on the controller board. A Line Module is required for each input.
Line Module
shield (terminate at controller only;
float at line module)
Question and Answer IconNeed help?

Do you have a question about the HIRSCH AEB8 and is the answer not in the manual?

HIRSCH AEB8 Specifications

General IconGeneral
BrandHIRSCH
ModelAEB8
CategoryController
LanguageEnglish

Summary

Testing AEB8 Installation

Self-Test and Verification

Covers system self-test output, verifying expansion inputs, and AEB status in controller configurations.

Command and Troubleshooting

Details using Command 88*2 for testing and troubleshooting connection issues if verification fails.

AEB8 Setup and Configuration

AEB8 Compatibility and Addressing

Explains AEB8 controller model compatibility and setting board addresses using J1 and J2 jumpers.

Mounting and Board Installation

Board Installation and Warnings

Details physical mounting steps, connecting EBIC, and provides a critical warning about specific controller boards.

AEB8 Wiring Procedures

Wiring and Connection Procedures

Covers preparing the enclosure, routing wires, connecting them to green connectors, and reattaching connectors.