A T PU MP WA TE R HEA TE R CO MPR ES SO R CRI TE RI A
PAGE:12/30
(6)The compressor can’t be used in the place with corrosive atmosphere such as hot
spring and chemical warehouse. It should not be the structure often splash water on the
surface of the compressor forcibly.
(7) The t
rouble of cross valve, electromagnetic valve, defroster, refrigerant controller,
fan motor used in refrigerating system may cause compressor accident .So their reliability
should
be ensured completely. Moreover, the way of design, manufacture, application of
refrigeration cycle with less-leak should be adopted.
(8)The main electric circuit should be equipped with fuse or breaker.
(9)Refrig
erant should be charged from the end of condenser of refrigerating systems. Never
Charge refrigerant to the compressor directly.
The
refrigerant should always be charged in liquid state. When the refrigerant is charged
in gas state. The percent component will possibly be changed.
(10) Temperatures within systems during stable compressor operation should not be less
than -35℃ to prevent wax precipitation from the oil.
(1
1) The units of refrigerating system should be connected to earth.
(1
2)Compressor mounting
Rubber grommets are designed soft to provide the noise isolation and to lessen vibration
Energy transmission. Stud bolt should be designed to provide sufficient clearance for
noise andvibration isolation and to prevent compressor from coming off its mount.
(13) There should be adequate clearance between the under-surface of Push-Nut and the
up
per surface of rubber grommets.