No. Item Optional function
Individual
Setting
Settings Setting conditions Description
2
b2
Circulation function at
heating thermo OFF
00
Function disabled
(factory setting)
This function keeps the fan running
during the thermo OFF sequence,
at the fan speed set on the remote
control switch, to prevent the
straticationofairintheroom.
01 Function enabled
3
b3
Not Used -
00
- Use as 00 conditions
01
4
b4
Changeofltercleaning
period
00 Standard (1200 hours)
This function is used to modify the
period of operation after which
theairltercleaningindicationis
shown in the remote control.
For RPK-FSN(H)3M models, the
factory setting is b4=00: Standard
setting 200 hours.
01 100 hours
02
1200 hours
(factory setting)
03 2500 hours
04 No indication
5
b5
Locking of operation mode ×
00
Function disabled
(factory setting)
This function prevents the
modicationoftheoperation
mode of the unit from the remote
controller and from central
controls, once it has been
selected.
01 Function enabled
6
b6
Locking of setting
temperature
×
00
Function disabled
(factory setting)
This function prevents the
modicationofthesetting
temperature of the unit from
the remote controller and from
central controls, once it has been
selected.
01 Function enabled
7
b7
Setting operation mode as
cooling only
×
00
Function disabled
(factory setting)
This function is used to limit the
operation mode to cooling only
and to prevent heating mode from
being enabled.
01 Function enabled
8
b8
Automatic COOL/HEAT
operation
×
00 Function disabled (factory setting)
This function enables the selection
of Auto cool/heat operation mode.
If the function is not activated, Auto
cool/heat mode cannot be selected
on the remote control switch.
01 Function enabled
9
bg
Locking of fan speed setting ×
00
Function disabled
(factory setting)
This function prevents the
modicationofthefanspeedof
the unit from the remote controller
and from central controls, once it
has been selected.
01 Function enabled
10
bA
Not available -
“- -”
permanent
Not available
11
bb
Cooling setting temperature
correction
×
00 No compensation (factory setting)
This function decreases the
setting temperature and is used to
produce longer cooling periods.
01
Setting temperature decreased by
1 ºC
02
Setting temperature decreased by
2 ºC
12
bC
Not used -
00
- Use at 00 conditions
01
13
bd
Not used -
00
- Use at 00 conditions
01
14
bE
Not used -
00
- Use at 00 conditions
01
15
C1
Not used -
00
- Use at 00 conditions
01
16
C2
Not available -
“- -”
permanent
-
17
C3
Not used -
00
- Use at 00 conditions
01