No. Item Optional function
Individual
Setting
Settings Setting conditions Description
22
C8
Control by the temperature
sensor of the remote control
switch
? NOTE
The remote control switch
shallbeinstalledinaproper
placeforthecorrectdetection
of room temperature by its
temperaturesensor.
00
Control by the air inlet sensor of
indoor units (factory setting)
Thisfunctionspeciesthe
temperature sensor to be used as
control sensor by the indoor unit.
01
Control by the temperature sensor
of the remote control switch
02
Control by the average value of
the air inlet sensor of indoor units
and the temperature sensor of the
remote control switch.
(Air inlet + Remote control switch)/2
Control sensor when a
remote sensor is connected
to the THM4 connector in the
indoor unit PCB
? NOTE
The remote sensor shall be
installedinaproperplacefor
thecorrectdetectionofroom
temperature.
Model
RPF(I)-FSN2E
00, 01, 02
When a remote sensor is connected
to THM4, this remote sensor is
used as control sensor, whichever
the setting for C8
(factory setting C8=00)
Control sensor when a
remote sensor is connected
to the THM4 connector in the
indoor unit PCB
? NOTE
The remote sensor shall be
installedinaproperplacefor
thecorrectdetectionofroom
temperature.
Models
RCI-FSN4
RCIM-FSN4E
RCD-FSN3
RPC-FSN3
RPI-FSN5E
RPI-FSN3E(P)E(-f)
RPIM-FSN4E(-DU)
RPK-FSN(H)3M
00, 02
Air temperature control using
the average value of the air inlet
thermistor and the remote sensor
(factory setting C8=00)
(Air inlet + Remote sensor)/2
01
Air temperature control using the
remote sensor
23
Cg
Not available -
“- -”
permanent
24
CA
Not available -
“- -”
permanent
25
Cb
Selection of forced stoppage
logic
00
Forced stoppage input: A contact,
normally open contact (factory
setting)
This function determines the logic
operation for the forced stoppage
contacts.
01
Forced stoppage input: B contact,
normally closed contact
26
CC
Not used -
00
- Use at 00 conditions
01
OPTIONAL FUNCTION
PMML0497 rev.1 - 12/2020