Priority
sequence
Error code
(LED on PCB)
Breakdown
list
Breakdown
description
Operation
11s ON + Blink onceF-sensor abnormalF-sensor value abnormalProvisional mode
21s ON + Blink twiceR-sensor abnormalR-sensor value abnormalProvisional mode
31s ON + Blink 3 timesTC-sensor abnormalTC-sensor value abnormalDisplay error code
41s ON + Blink 4 timesD-sensor abnormalD-sensor value abnormalNo defrosting
5Blink twice
EEPROM data
abnormal
EEPROM data
abnormal
Display error code
6Blink 12 times
R-Fan motor abnormal
or 12V drops
R-Fan motor abnormal
or 12V drops
R-Fan motor stops and retry after 3min.
7Blink 4 times
Defrosting circuit
abnormal
Defrosting continues
even after 2 hours
After 2 hours,stop defrosting
and display error code
83s ON + Blink onceFreezer not cool
F-sensor stays over -10℃
for 72 hours
Display error code
93s ON + Blink twiceRefrigerator not cool
R-sensor stays over 10℃
for 72 hours
Display error code