– 6 –
a
b
o
u
t
0
.
5
m
2
1
above 300 mm
Maximum pipe length 30m
Minimum pipe length 3m
must not bend
above 2300 mm
above
200 mm
above 50mm
above 100mm
Be sure to
completely
seal any
gap with
putty.
700
Figure showing the installation of Indoor and Outdoor unit
● The difference in height
between the indoor and
outdoor unit should be kept
max 20m.
● The connecting pipe, no
matter big or small, should
all be insulated with
insulation pipe and then
wrapped with vinyl tape.
(The insulator will
deteriorate if it is not
wrapped with tape).
The connection of insulated
drain hose.
Please use insulated drain
hose for the indoor piping
(commercial product).
The indoor piping should be
insulated with the enclosed
insulation pipe. (If the
insulator is insufficient,
please use commersial
products).
inner diameter ø 16mm