Hitachi RAS-08PH1 - Page 69

Hitachi RAS-08PH1
114 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The v
2. Power circuit for P.W.B.
oltage specification of the power circuit is as follows.
<Check points>
Output Voltage Main load Measuring points Potential failure modes
spec. +
12V 11-13V MAIN P.W.B. R117 (“12V” display) R117 (“0V” display) The unit won’t operate
MAIN P.W.B. error
5V 4.5-6V MAIN P.W.B. C123+ (“5V” display)
L105 (“15V” display) R117 (“0V” display)
R117 (“0V” display) The unit won’t operate
MAIN P.W.B. error
B-12V 11-16V Expansion valve L104 (“B-12V” display)
R110 (“B-0V” display)
LD301 blinks 5 times;
Expansion valve error
15V 14-17V DC fan motor (CN24) LD301 blinks 3 times,
MAIN P.W.B.
35V 33.5-38V Indoor unit electrical parts D103
R109 (“0V-35V” display)
Indoor unit
Abnormal low speed rotation
won’t operate
(Terminal C,D) (C-35V” display) Terminal D (red line)
Reversing valve (CN2) Terminal C (blown line)
Check each voltage. If each voltage meets the voltage specification above, the power circuit is normal.
If any error is found after checking, remove all loads and recheck each voltage.
If no error is found in this step, the power circuit is normal. Check the removed loads.
If any error is found in this step, the power circuit has any failure. Replace the power circuit for P.W.B.
* A short-circuited load may cause an output error not only in the load but also in the others. Be sure to
check all outputs of the loads.
* Be sure to wait 15 minutes or more in order to discharge all the remaining voltage in the circuit to
connect/disconnect the wiring, other wise, the components may be damaged.
The failures of the loads are as follows.
Failed
output
35V
15V
12V, 5V
Criterion
Connect the cable correctly.
Remove the connection cable and measure the
voltage. If the voltage is correct, check the electrical
parts for the indoor unit.
Remove the CN2 and measure the voltage. If the
voltage is correct, check the reversing valve.
Check the main P.W.B.
Possible causes
Reversed connection of the cable.
Electrical part for the indoor unit has
a failure.
Short-circuited reversing valve
DC fan motor error
Main P.W.B. error
Main P.W.B. error
Remove the CN24 and measure the voltage.
If the voltage is correct, check the DC fan motor.
Also, check the main P.W.B. 1 A fuse for blow
out in this step.
69