4. Capacity and selection data
TCGB0075 rev.0 - 11/2012
72
a.ii) Use of auxiliary heating source (electric heater or boiler combination)
In installations which already have a conventional boiler (gas/oil), it can be used to alternate with YUTAKI S80 (Bi-valent
system) which it will help to increase the overall performance of the whole installation signicantly.
Equally, if an additional heat load is required, an electric heater can be installed as accessory for the Mono-energy system.
In any case, the Procedure description explained before can be applied to all the energy systems mentioned but includ-
ing a heat load check when using auxiliary heating source (Mono-energy or Bi-valent systems) and recalculating the new 
heating points.
It will be checked that the combination (YUTAKI S80 + electric heater / boiler) covers the temporary needs in the coldest
days of the year.
Mono-energy and Bi-valent systems are usefull when there is a constant regular heating load and low periods of heating
load peaks related to the coldest days of the year.
N O T E
The following check can be used as well for the two combinations.
•  Step 1: Initial pre-selection
Proposed energy system Mono-energy
Inlet/outlet water temperature 47/55 ºC
Regular ambient temperature WB/DB
(HR = 85%)
-5/-4 °C
Required regular heating load 9.0 kW
Ambient temperature WB/DB on the coldest
day of the year (HR = 85%)
-10/-9 ºC
Heating load required on the coldest day of
the year
13.0 kW
Installation restrictions
Installation type Radiant oor
Power supply 1~ 230V 50Hz
Indoor unit lower than outdoor unit 15 m
Equivalent piping length between outdoor
and indoor unit
20 m
13.0 kW, -10 ºC WB
Capacity of
YUTAKI S80
Heating capacity
Outdoor ambient temperature
9.0 kW, -5 ºC WB
Heating load
demanded
In this new system the heat pump meets with the regular heating load. To reach the peak heating load of 13.0 kW (-10
ºC WB) necessary in the coldest days of the year the electric heater can provide the auxiliary heating capacity to cover it.