Blocked in Inlet Side
The length A is as shown in the following table:
L A
0 < L 1/2H
600 or greater
1/2H < L H
1200 or greater
Be sure to use the fan direction guide. Allow 100 mm of space between units. Leave open both right and left sides. Serial installation allowed up to two
units.
Outlet Side Blocked
Upper Side Open
Single Installation Multiple Installation (Two units or more)
Allow 100 mm of space between units. Both right and left sides shall be
open.
Be sure to use the fan direction guide. Leave open both right and left sides.
Be sure to use the fan direction guide. Allow 100 mm of space between
units. Serial installation allowed up to two units. Leave open both right and
left sides.
The length A is as shown in the following table:
L A
0 < L 1/2H 200
1/2H < L H 300
When L > H, use a base for outdoor unit to make L H.
Close the base not to allow the outlet air bypassed.
The length A is as shown in the following table:
L A
0 < L 1/2H 250
1/2H < L H 350
When L > H, use a base for outdoor unit to make L H.
Close the base not to allow the outlet air bypassed.
2 Unit Installation
17
SMGB0060 rev. 1- 12/2010