9 Servicing
RPIM-(0.6-1.5)FSN4E - Ducted indoor unit
SMGB0099 rev.0 - 12/2016
306
9.8.5  Removal of the oat switch
? NOTE
To  disconnect  and  remove  the  oat  switch,  previously  see  the  chapter 
corresponding to the wiring diagrams in this Manual.
1  Remove the necessary covers to access the oat switch.
2  Loosen the screws securing the oat switch to the support. 
? NOTE
The torque value of the resin nut is 0.3 - 0.4 Nm. If the torque value is 
higher, the nut will be damaged.
Nº Part
1 Float switch position
3  Loosen the resin nut securing the oat switch and remove it.
Nº Part
1 Float switch
9.8.6  Removal of the air lter
1  Remove the air lter xture support screws and remove the air 
lter.
Nº Part
1 Air lter xture bar
2  Pull the air lter downwards.
Nº Part
1 Air lter
2 Screws
3 Air lter xture bar