9 Servicing
KPI-(252-2002)(E/X)4E - Energy recovery and active energy recovery ventilation units
SMGB0099 rev.0 - 12/2016
340
9.11.10  Removal of the fan motor
1  Remove all 4 screws from the fan service cover (d)
2  Unplug the connector that is inside the protection cap
3  Remove all 4 screws from the fan assy (e)
? NOTE
Use a 5 mm allen key (hexagon key)
4  Remove the fan with the assembled cover
! CAUTION
The  fan  kit  is  not  xed,  pay  attention  when  all  4  screws  are 
removed, the fan can fall.
In order to remove de cover from the fan, unscrew all 4 screws.