19 SAFETY AND CONTROL DEVICE SETTING
Model
RCIM-0.6FSN4, RCIM-0.8FSN4, RCIM-1.0FSN4, RCIM-1.5FSN4,
RCIM-2.0FSN4, RCIM-2.5FSN4
For Evaporator Fan Motor Automatic Reset, Non-Adjustable
Internal Thermostat Cut-Out ºC 100+4
For Control Circuit
Fuse
Capacity A 5
Freeze Protection
Thermostat
Cut-Out ºC 0
Cut-In ºC 14
Thermostat
Differential ºC 2
Safety and control device setting
PMML0363A rev.2 - 08/2016 - P541655942