UNITS INSTALLATION
PMML0385 rev.2 - 12/2018
7
EN
3 UNITS INSTALLATION
! DANGER
• Checktoensurethattheaccessoriesarepackedwiththeindoor
unit.
• Donotinstalltheindoorunitsoutdoors.Ifinstalledoutdoors,an
electrichazardorelectricleakagewilloccur.
• Considertheairdistributionfromeachindoorunittothespace
oftheroom,andselect a suitablelocationsothatuniformair
temperatureintheroomcanbeobtained.Itisrecommendedthat
theindoorunitsbeinstalled2.3to3metersfromtheoorlevel.If
theunitisinstalledhigherthan3meters,itisalsorecommended
that a fan be utilised to obtain uniform air temperature in the
room.
• Avoid obstacles which may hamper the air intake or the air
dischargeow.
• Payattentiontothefollowingpointswhentheindoorunitsare
installedinahospitalorotherplaceswherethereareelectronic
wavesfrommedicalequipment,etc.
• Donot install the indoor units where electromagnetic wave is
directly radiated to the electrical box, remote control cable or
remotecontrolswitch.
• Installtheindoorunitsandcomponentsasfaraspracticalorat
least3metersfromtheelectromagneticwaveradiator.
• Prepareasteelboxandinstalltheremotecontrolswitchinit.
Prepareasteelconduittubeandwiretheremotecontrolcablein
it.Thenconnectthegroundwirewiththeboxandtube.
• Installanoiselterwhenthepowersupplyemitsharmfulnoises.
• Thisunitisexclusivenonelectricalheatertypeindoorunit.Itis
prohibitedtoinstallaelectricalheaterintheeld.
• Mount suspension bolts using M10 (W3/8) as size, as shown
below:
• Donotputanyforeignmaterialintotheindoorunitandcheckto
ensurethatnoneexistintheindoorunitbeforetheinstallation
andtestrunning.Otherwiseareorfailure,etc.,mayoccur.
! CAUTION
Do not install the indoor units in a ammable environment to avoid a
re or an explosion.
Check to ensure that the ceiling slab is strong enough. If not strong
enough, the indoor unit may fall down on you.
Do not install the indoor units, outdoor unit, remote control switch and
cable within approximately 3 meters of strong electromagnetic wave
radiators such as medical equipment.
Do not install the indoor units in a machinery shop or kitchen where
vapor from oil or mist ows to the indoor units. The oil will deposit on
the heat exchanger, thereby reducing the indoor unit performance,
and may deform. In the worst case, the oil damages the plastic parts
of the indoor unit.
To avoid any corrosive action to the heat exchangers, do not install
the indoor units in an acid or alkaline environment.
When lifting or moving the indoor unit, use appropriate slings to avoid
damage and be careful not to damage the insulation material on units
surface.
I-Beam
Suspension Bolts
(W3/8 or M10)
For Concrete
Slab 150~160mm
Sling Bolt
(W3/8 or M10)
Square
washers
Wooden Bar
(60mm to 90mm Square)
Steel
Concrete
Nuts
Anchor Bolt
Wooden Beam
3.1 UNIT INSTALLATION
3.1.1 Installation
Install the indoor unit with a proper clearance around it paying careful attention of installation direction for the piping, wiring and
maintenance working space, as shown below.
Service Space
RPI-0.4FSN5E RPI-(0.6-1.5)FSN5E
(mm)