16
REFRIGERANT PIPING
Ó
CAUTION:
Cautions for Refrigerant Pipe Ends
When installing pipe through the wall, secure a cap at
the end of the pipe.
Do not place the pipe directly on the ground
Position of Piping Connection for Outdoor Unit
Connect the pipebs with the liquid line stop valve and the
gas line stop valve at the outdoor unit as shown.
RAS-5-8FSN
RAS-10-30FSN
MODEL A B C D E F 1 2
RAS-5FSN
138 242 232 306 155 155 15.88 9.53
RAS-8FSN(E)
137 241 238 306 155 156 19.05 9.53
RAS-10FSN(E)
137 227 247 306 151 156 22.2 9.53
RAS-16FSN
137 227 254 295 171 173 28.6 12.7
RAS-20FSN
137 233 247 287 141 150 28.6 15.88
RAS-24FSN
138 234 247 274 159 171 28.6 15.88
RAS-30FSN
138 234 247 274 159 171 31.75 19.05
NOTE:
1: Ø Refrigerant Gas Piping Connection.
2: Ø Refrigerant Liquid Piping Connection.
RAS-8/10FXN(E)
RAS 16~30FXN
MODEL A B C D E F G H I
RAS-8FXN(E)
119 195 284 305 253 247 151 156 156
RAS-10FXN(E)
119 195 284 305 253 247 151 156 156
RAS-16FXN
115 183 292 385 253 246 139 146 150
RAS-20FXN
118 186 295 381 253 246 139 146 146
RAS-24FXN
110 172 281 379 253 247 159 171 178
RAS-30FXN
110 172 281 379 253 247 159 171 178
MODEL 1 2 3
RAS-8FXN(E)
19.05 15.88 9.53
RAS-10FXN(E)
22.2 19.05 9.53
RAS-16FXN
28.6 22.2 12.70
RAS-20FXN
28.6 22.2 15.88
RAS-24FXN
28.6 25.4 15.88
RAS-30FXN
31.75 28.6 19.05
NOTE:
1: Ø Refrigerant Gas Piping Connection.
2: Ø Refrigerant Gas high Piping Connection
3: Ø Refrigerant Liquid Piping Connection
Pipes can be connected from 3 directions
Correct
Incorrect Correct
Incorrect
Correct
Incorrect
Rain Water
can enter
A
ttach cap o
r
vinyl tape
A
ttach cap or vinyl tape
Bottom Base
Front Side
Bottom Side
Rear Side