20
ADDITIONAL CHARGE OF REFRIGERANT R410A
15. ADDITIONAL CHARGE OF REFRIGERANT R410A
Additional Charge of Refrigerant R410A
Although refrigerant has been charged into this unit, it is
required that additional refrigerant be charged according to
piping length and indoor units.
A. Determine the additional refrigerant quantity according
to the following procedure, and charge it into the system.
B. Record the additional refrigerant quantity to facilitate
service activities thereafter.
1. Calculating Method of Additional Refrigerant Charge
(W kg)
Calculate the additional refrigerant charge amount
according to the following method 1.1 to 1.3.
1.1.Additional Refrigerant Charge Calculation for Liquid
Piping (W1 kg)
Calculate the additional refrigerant charge amount for
liquid piping as below and see example for model
RAS-8FSN, and fill in the following table.
Example
Piper Diameter
(mm)
Total Pipe
Lenght (m)
Additional
Charge (Kg/m)
Sub Total
Amount (Kg)
22.2 0 0.390 0 x 0.390 = 0
19.05 0 0.280 0 x 0.280 = 0
15.88 0 0.190 0 x 0.195 = 0
12.7 0 0.120 0 x 0.120 = 0
9.53 51 0.07 51 x 0.07 = 3.57
6.35 5+3+5+3+5+3 0.03 24 x 0.03 = 0.72
Total Additional Charge Amount for Liquid Pipe (W1) = 4.29 kg
This system (Fill in the following table)
Piper Diameter
(mm)
Total Pipe
Lenght (m)
Additional
Charge (Kg/m)
Sub Total
Amount (Kg)
22.2 0.390
19.05 0.280
15.88 0.190
12.7 0.120
9.53 0.07
6.35 0.03
Total Additional Charge Amount for Liquid Pipe (W1) =           kg
Ô
ATTENTION:
Is NOT necessary refrigerant charge for indoor units.
1.2  Determine the number of indoor units which require
the additional refrigerant charge
Outdoor Unit
W0 Outdoor Unit Ref.
Charge (Kg)
RAS-5FSN 5.4
RAS-8FSN(E) 8.5
RAS-10FSN(E) 9.5
RAS-16FSN 13.0
RAS-20FSN 19.0
RAS-24FSN 23.0
RAS-30FSN 26.0
Outdoor Unit
W0 Outdoor Unit Ref.
Charge (Kg)
RAS-8FXNE 8.5
RAS-10FXNE 9.5
RAS-16FXN 19.0
RAS-20FXN 19.0
RAS-24FXN 26.0
RAS-30FXN 26.0
Horse Power  W2 Add. Charge (Kg)
0.8 0
1.0 0
1.5 0
2.0 0
2.5 0
3.0 0
4.0 0
8.0 1.0
10.0 1.0
NOTE:
W
0
 is Outdoor Unit refrigerant charge before shipment.
H1d50m (Position of outdoor unit is higher)
H1d40m (Position of outdoor unit is Lower)
Outdoor Unit
Provide oil trap to gas line at
every Ht meters lift
ctual Ltd100m
Equivalent Ltd125m