32
SAFETY AND CONTROL DEVICE SETTING
19. SAFETY AND CONTROL DEVICE SETTING
Safety and Control Device Setting for Indoor Units
Model RCI RCD RPC RPI RPK RPF RPFI Remarks
For Evaporator Fan Motor
Internal Thermostat
Cut-Out
Cut-In
°C
°C
145±5
90±15
130±5
83±15
135±5
90±15
140±5
90±15
130±5
83±15
130±5
83±15
130±5
83±15
Automatic Reset, Non-
adjustable (each one
for each motor)
For Control Circuit
Fuse Capacity A
5
Freeze Protection
Thermostat
Cut-Out
Cut-In
°C
°C
0
14
Thermostat Differential °C 2
Safety and Control Device Setting for Outdoor Units
Model
RAS-5 RAS-8 RAS-10 RAS-16 RAS-20 RAS-24 RAS-30
Automatic Reset, Non-Adjustable
(each one for each compressor)
For Compressor
Pressure Switches
High Cut-Out
MPa
05.0
15.0
4.15
Cut-In MPa
3.20 r 0.15
Fuse
3~, 380/415, 50Hz A 20x2 20x4 20x4 20x6 20x8 20x10 20x12
FSN 40 40 x 3 40 x 4 40 x 5 40 x 6
Oil Heater
Capacity
FXN
W
-
40 x 2 40 x 2
40X4 40 x 5 40 x 6 40 x 7
Non-Adjustable
CCP Timer
Setting Time
min
3333333
Automatic Reset, Non-Adjustable
(each one for each compressor)
For Condenser Fan Motor
Internal Thermostat
Cut-Out
Cut-In
ºC
ºC
130r5
83r15
130r5
83r15
130r5
83r15
130r5
83r15
130r5
83r15
130r5
83r15
130r5
83r15
For Control Circuit
Fuse Capacity on
PCB
A
12 12 12 12 12 12 12
CCP Timer: Enforced 3 minutes operation and stoppage.