8.6.2.7  Swimming Pool
Available if Controller type (LCDM)= “Unit” or “Unit + Room”.
•  Status 
•  Setting Temperature
•  Offset Temperature 
REF Access Description
Default 
Value
Range Steps Units Application
Notes
Swimming Pool
S SC S80 M
SWP Status  Disabled
Disabled / 
Enabled
- - ○ ○ ○ ○ -
SWPs Setting Temperature  24 24~33 1 ºC ○ ○ ○ ○ (*1)
SWoff Offset Temperature 15 10~A 1 ºC ○ ○ ○ ○ (*1)(*)
? NOTE
•  (*1): If Status (SWP)= “Enabled”.
•  (*) Refer to the table:
Model
YUTAKI S & COMBI YUTAKI S80 YUTAKI M
(2.0-3.0)HP REST (4.0-6.0)HP 3HP REST
A A 31 36 56 (1) 36
 - (1) If R134a compressor disabled (DSW4#1:ON) the setting must be 36ºC.
8.6.2.8  Complementary Heating
Available if Controller type (LCDM)= “Unit” or “Unit + Room”.
•  Heating Source 
•  Electrical Heater   (*1)
•  Boiler Combination   (*2)
•  Solar Combination 
? NOTE
(*1): Available if Heating source (HES)= “HP+Heater” or “HP+Heat.+Boil.”.
(*2): Available if Heating source (HES)= “HP+Boiler” or “HP+Heat.+Boil.”.
UNIT CONTROLLER
PMML0335A rev.1 - 04/2016
152