Start-up and Operation: Checktoensurethatallthestopvalvesarefullyopenedandnoobstacleexistsattheinlet/outletsides
beforestart-upandduringtheoperation.
Maintenance:Periodicallycheckthehighpressuresidepressure.Ifthepressureishigherthanthemaximumallowablepressure,
stopthesystemandcleantheheatexchangerorremovethecause.
Maximum Allowable Pressure and High Pressure Cut-out Value:
Refrigerant Maximum Allowable Pressure (MPa) High Pressure Switch Cut-out Value (MPa)
R410A 4.15 4.00 ~ 4.10
? NOTE
ThelabelforthevesselunderPEDareattachedonthehighpressurevessel.Thepressurevesselcapacityandvesselcategoryareindicatedonthe
vessel.
Location of High Pressure Switch
Compressor
? NOTE
Thehighpressureswitchisindicatedontheelectricalwiringdiagramin
theoutdoorunitasHPSconnectedtoprintedcircuitboard(PCB1)inthe
outdoorunit.
Structure of High Pressure Switch
Contact Point Pressure Detected
Connected to the electrical wire
! DANGER
• Donotchangethehigh-pressureswitchlocallyorchangethe
highpressurecut-outsetvaluelocally.Ifchanged,itwillcause
seriousinjuryordeathduetoexplosion.
• Donotattempttoturnservicevalverodbeyonditsstop.
4 TRANSPORTATION AND HANDLING
When hanging the unit, ensure a balance of the unit, check
safety and lift it up smoothly.
Do not remove any packing materials.
Hang the unit under packing condition with two ropes.
For safety reasons ensure that the outdoor unit is lifted smoothly
and does not lean.
Model Gross Weight (kg)
RAS-(4-6)WH(V)NPE 116
RAS-8WHNPE 152
RAS-10WHNPE 154
RAS-(4-10)WH(V)NPE
0.7 -1.0
> 60º
5 BEFORE OPERATION
! CAUTION
• Supply electrical power to the system for approximately 12 hours
before start-up or a long shutdown. Do not start the system
immediatelyafterpowersupply,itmaycauseacompressorfailure
becausethecompressorisnotheatedwell.
• Whenthesystemisstartedafterashutdownlongerthatapproximately
3months,itisrecommendedto check thesystem by yourservice
contractor.
• TurnOFFthemainswitchwhenthesystemistobestoppedforalong
periodoftime:IfthemainswitchisnotturnedOFF,electricitywillbe
used,becausetheoilheaterisalwaysenergisedduringcompressor
stopping.
• Makesurethattheoutdoorunitisnotcoveredwithsnoworice.If
covered,removeitbyusinghotwater (approximately50°C).If the
watertemperatureishigherthan50°C,itwillcausedamagetoplastic
parts.