Page #57 background imageLoading...
Page #57 background image
2 General data
Component data
TCGB0123 rev.2 - 10/2019
49
2
Model
RWD-2.0NRWE-
(200/260)S(-K)(-W)
RWD-2.5NRWE-
(200/260)S(-K)(-W)
RWD-3.0NRWE-
(200/260)S(-K)(-W)
Expansion vessel
Material - Steel (with stainless/galvanized steel connections)
Internal water volume L 6.0
Working pressure bar 3.0
Pre-loading pressure
(Air side)
bar 1.0
Water strainer
Type - Isolated water strainer (Filter ball)
Material - Brass
Piping connection (in.) 1”, DN25
Mesh (hole size) mm 0.7
Self-cleaning(withbackush)lter - Yes
DHWT Pressure and temperature
relief valve (1)
bar 7
ºC 96
Safety valve - Yes (3 bar)
Low pressure switch - Yes (<0.5 bar)
Unit drain port - Yes
DHW drain valve - Yes
Shut-off valve - Yes (2 factory-supplied valves)
Air purger - Yes
Manometer - Yes
Unit controller - Yes (PC-ARFH1E)
(1) Only for UK version.

Table of Contents

Other manuals for Hitachi YUTAKI S COMBI Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi YUTAKI S COMBI Series and is the answer not in the manual?

Hitachi YUTAKI S COMBI Series Specifications

General IconGeneral
TypeAir-to-Water Heat Pump
Energy Efficiency Class (Cooling)A++
RefrigerantR32
Operating Temperature Range (Heating)-20°C to 35°C
Energy Efficiency Class (Heating)A+++
Integrated DHW Tank190 liters
Dimensions (Indoor Unit)Varies by model
Dimensions (Outdoor Unit)Varies by model
Weight (Indoor Unit)Varies by model
Weight (Outdoor Unit)Varies by model
Operating Temperature Range (Cooling)+10°C to +46°C