EasyManua.ls Logo

Hitecsa ACVBZ Series - Page 9

Hitecsa ACVBZ Series
16 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9
Nominal cooling capacity (kW) of one circuit
Pressure drop per 10 m. of equivalent length
Suction / discharge line. Vertical
pipe run - Fig. 3
- For heat pump systems use a trap
at the base of the vertical pipe run.
- There is no need for intermediate
trap.
- For cooling only systems traps are
not required.
- For heat pump systems keep veloc-
ity in the vertical run of suction or
discharge line more than 6 m/s.
For both options the following condi-
tions should be observed:
- The maximum allowable speed in all
gas lines is 15 m/s.
- The suction line must have insula-
tion and a slope of 1-2% toward the
compressor in the horizontal pipe
run.
- For long piping run it may be neces-
sary to adjust oil charge (see table
2). For each trap and for 10 m. of
pipe above 20 m. add oil.
- In the case of downward liquid flow
with a height exceeding 10 m. it is
necessary to install a manual pres-
sure equalization valve.
- Keep liquid subcooling at least 1°C
at the restrictor inlet. If the liquid
line has upward flow and pipe
length exceeding 15 m., for each 3.5
m. above this value provide 1°C
subcooling. In the cooling systems
subcooling can be obtained by the
contact of liquid and suction line (on
a max. length of 15 m.) creating the
heat exchange.
- For every meter of piping installed
add refrigerant according with the
table 1.
Graph 1 - Suction line
Nominal cooling capacity (kW) of one circuit
Diameter
Speed m/s
Pressure drop per 10 m. of equivalent length
Graph 2 - Discharge line
Speed m/s
Diameter
Table 2: ADDITIONAL OIL CHARGE
Diam. 3/8" 1/2" 5/8" 3/4" 7/8" 1-1/8" 1-3/8" 1-5/8"
cm³/10m 1.5 3 5 9 16 35 54 80

Related product manuals