Installation
CAUTION
Please observe the following to ensure that the
C6097 is not damaged during installation and
operation:
Continuous operation with gases containing
more than 0.1%-by-vol. H
2
S or ozone con-
centrations exceeding 200µg/m
3
accelerate
the ageing of elastomer materials and reduce
the service life.
Use approved sealing material only.
Dropping the device can cause permanent dam-
age. In this event, replace the entire device and
associated modules before use.
Check max. ambient temperature – see
page3 (Technical data).
When using silicone tubes, only use silicone
tubes which have been sufficiently cured.
Vapours containing silicone can adversely affect
the functioning of electrical contacts.
Condensation or vapours containing silicone
must not be allowed to get into the housing.
At subzero temperatures, malfunctions/failures
due to icing can occur.
When installing outdoors, place the C6097 in
a roofed area and protect from direct sunlight
(even IP65 version).
Avoid strong impact on the unit.
In case of highly fluctuating pressures, install a
restrictor orifice (Order No.75456321).
Installation position as required, preferably with
vertical diaphragm. Then the switching point p
S
corresponds to the scale value SK set on the
hand wheel. In other installation positions, the
switching pointp
S
will change and no longer
correspond to the scale valueSK set on the
hand wheel. Check the switching point.
p
s
= SK
p
s
=SK + 0.18 mbar p
s
= SK - 0.18 mbar
The C6097 must not be in contact with masonry.
Minimum clearance 20 mm.
Ensure that there is sufficient installation space.
Ensure unobstructed view of the hand wheel.
1 Disconnect the system from the electrical power
supply.
2 Shut off the gas supply.
3 Ensure that the pipeline is clean.
2
1
3
4
1 and 2 for
positive pressure (Rp ¼)
3 and 4 for
negative pressure (Rp
1
/8)
Connect Seal Free
Positive
pressure
C6097
1 2 3 or 4
2 1 3 or 4
Negative
pressure
C6097
3 4 1 or 2
4 3 1 or 2
Differential
pressure
C6097
1 or 2 for higher absolute pressure.
3 or 4 for lower absolute pressure.
Seal the ports that are not in use.
CAUTION
Ports 3 and 4 are connected to the upper dia-
phragm chamber with the micro switch.
For this reason, pipes carrying gas must not be
connected to port 3 or 4.
A filter pad at port4 protects the electrical con-
tacts in the C6097 from dirt particles in the sur-
rounding air or in the medium.
Filter pad for port3/4, see PartDetective.
Wiring
CAUTION
Please observe the following to ensure that the
C6097 is not damaged during operation:
Note the switching capacity, see page 3
(Technical data).
In the case of low switching capacities, such as
24V, 8mA, for example, we recommend using
an RCmodule (22Ω, 1μF) in air containing
silicone or oil.
1 Disconnect the system from the electrical power
supply.
M16 x 1,5:
ø 4–10 mm
3 42
5 6 7
Contacts 3 and 2 close when subject to increas-
ing pressure. Contacts 1 and 3 close when sub-
ject to falling pressure.
NO
2
NC
1
COM
3
L1
COM
3
NC
1
NO
2