Installation and Service Instructions for CX Weather-Sealed
ISSUE 4
Explosion-proof Switches
PK 88136
0518
Sensing and Control
WARNING
IF USED IN APPLICATIONS CONCERNING HUMAN
SAFETY
Only use NC direct opening (“positive
opening”/”positive break”) contacts, identified by the
symbol .
Do NOT use flexible/adjustable actuators. Only use
actuators designed for safety applications.
Do NOT defeat, tamper, remove, or bypass this
switch.
Hazardous voltage, disconnect power before
servicing.
Strictly adhere to all installation and maintenance
instructions.
Consult with local safety agencies and their
requirements when designing a machine-control
link, interface and all control elements that affect
safety.
Failure to comply with these instructions could
result in death or serious injury.
GENERAL INFORMATION
Sealed construction for Honeywell CX explosion-
proof switches provides protection from the entry of
water, dust and oil as defined in NEMA 3, 4, 4X, 6,
6P, 13, and IP66/IP67 as defined in IEC 529.
CX Series products with conduit types ¾-14NPT
also meet the North American Hazardous Locations
Designation: Class I, Group C and D; Class II,
Groups E, F and G. CX listings beginning with
numbers 14, 16, 24, 26, 36, or 84 (example: 14CX1)
also meet Class I, Group B. These explosion-proof
and weather-sealed switches are protected from
flammable hydrocarbon atmospheres, metal dust,
coal dust, and grain dust, and comply with UL
Standard: UL 894 and UL 1203, CSA Standard:
C22.2 no. 25-1966, C22.2 no. 30-M1986.
Select CX Series products also meet the European
Hazardous Locations Designation: EExd IIC T6
category II 2 GD, KEMA 01ATEX2111X and
complies with the European Directive on Equipment
and Protective Systems Intended for Use in
Potentially Explosive Atmospheres (94/9/EC)
commonly referred to as the ATEX Directive.
Compliance with the Essential Health and Safety
Requirements has been assured by compliance with
EN50014 1997, EN50018 1994 and EN50281-1-1.
The European-approved products have a
temperature range of –40 °C to 70 °C [–40 °F to
158 °F], and when used within the maximum voltage
and current specified on the product will have no
heating problems. Notice: As ambient temperature
approaches 60 °C [140 °F], the cable entry can be
70 °C [158 °F] or higher. Cable branching can be
80 °C [176 °F] or higher, making it important to select
cable that meets these requirements.
Application Note: Enclosures are based, in
general, on the broad definitions outlined in NEMA
standards. Therefore, it will be necessary for the user
to determine that a particular enclosure is adequate
when exposed to the specific conditions that might
exist in intended applications. Except as might
otherwise be noted, all references to products
relative to NEMA enclosure types are based on
MICRO SWITCH evaluation only.
IMPORTANT: Switches without shaft re-storing
force do not have overtravel stops. On switches with
potentiometers, use care to insure that overtravel
does not exceed 125° in the application and during
set-up.
LEVER POSITIONING
Loosen the screw with a 9/64 inch hexagon key
wrench, move the lever to the desired position and
securely tighten the screw until the "teller tab" can no
longer be moved by hand. Then tighten the screw
another 1/8 to 1/4 turn to assure that the lever is tight
on the shaft. Hexagon key wrenches are provided in
adjusting tool set LSZ4005 for this purpose.
CAM ADJUSTMENT
Pretravel, overtravel, and actuation sequencing
can be adjusted and/or modified in the field. No tools
are required.
To Adjust Plunger Types:
1. Lift cam follower.
Question and Answer IconNeed help?

Do you have a question about the Honeywell CX Series and is the answer not in the manual?

Honeywell CX Series Specifications

General IconGeneral
BrandHoneywell
ModelCX Series
CategorySwitch
LanguageEnglish

Summary

General Information and Safety

Human Safety Warnings

Crucial safety instructions for applications concerning human safety, emphasizing NC contacts and specific actuator types.

Lever Positioning

Instructions for adjusting lever position using a 9/64 inch hexagon key wrench for secure and proper fit.

Cam Adjustment

Field adjustment procedures for pretravel, overtravel, and actuation sequencing without requiring special tools.

Product Specifications and Ordering

Replacement Parts

Details on replacement switch assemblies including basic switches, cam wheels, and springs for maintenance.

How to Order Replacement Assemblies

Guidelines for converting complete switch catalog listings to replacement assembly catalog listings.

Analog Position-Sensing Units

Specifications and wiring diagrams for resistive and 4-20 mA current output analog sensing units.

Setup and Wiring for Analog Output

Setup Instructions for 2-Wire Analog

Procedures for setting up and repositioning the shaft for 4 to 20 mA output units.

Wiring Diagram and Adjustment

Connecting power, adjusting null offset and span potentiometers for 4-20 mA output.

Mounting and Compliance Details

Assemble Cover Lock Bracket

Instructions for assembling the cover lock bracket for European compliance and proper grounding.

Mounting Dimensions

Detailed dimensions for rotary and plunger housings, including porting and mounting hole information.

Important Warnings and Warranty

Product Opening Hazard Warning

Warning against opening energized products in flammable gas atmospheres to prevent injury or death.

Improper Conduit Thread Warning

Warning against using incorrect conduit threads to maintain explosion-proof integrity.

Warranty and Remedy Information

Details on Honeywell's product warranty, remedy, and contact information for support and specifications.