L7148F ELECTRONIC AQUASTAT
®
CONTROLLER
68-0189—2 6
Table 2. Sequence of Operation
Fig. 4. Wiring L7148F with multizone valves.
Thermostat
Operation
Mode Burner Circulator
Off Normal Off Off
Off High Limit Off Off
On Normal On On
On High Limit Off On
Either Reset Off Off
POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
GROUND MUST BE AN EARTH GROUND CONNECTION.
ADD JUMPER AS SHOWN.
FOR EXTERNAL TRANSFORMER VA REQUIREMENTS,
REFER TO APPLICATION SECTION.
B1 AND S1 ARE 3/16 INCH. QUICK CONNECT TERMINALS
ALL OTHER TERMINALS ARE 1/4 INCH.
C, COM, Z, B2, G ARE ALL CONNECTED INSIDE DEVICE.
R IS A CONVENIENCE TERMINAL FOR 24V HOT
CONNECTION FOR USE WITH IGNITION CONTROLS.