Installation Guide
r
Follow the procedure below to configure the thermostat to match the installed
heating/cooling system, and customize feature operation as desired.
Function Setting
number
To begin, press and hold the A and FAN
buttons until the display changes
Press A or T to change settings
Press N_T to advance to next function
Press DONEto exit and save settings
Setup Function
1 system type
Settings & Options
0 Gas_ oil or electric heat with air conditioning
1 Heat pump
2 Heat only (2-wire systems/power to open & close zone valves/
normally open zone valves)
3 Heat only with fan
4 Cool only
2 Changeover valve 0
(O/B terminal) 1
3 Fan control 0
(heating) 1
5 Heating cycle rate 5
(CPH: cycles/hour) 1
3
9
9 Compressor 3
cycle rate (CPH)
12 System setting 0
adjustment 1
2
Changeover valve (O/B terminal energized in cooling)
Changeover valve (O/B terminal energized in heating)
Gas or oR furnace -- equipment controls fan in heating
Electric furnace -- thermostat controls fan in heating
For gas or oil furnaces of less than 90% efficiency
For steam or gravity systems
For hot water systems & furnaces of over 90% efficiency
For electric furnaces
[Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH]
Recommended for most compressors
[Other cycle rate options: 1, 2, 4, 5 or 6 CPH]
Manual changeover (Heat/Cool/Off)
Auto changeover (Heat/Cool/Auto/Off) **See page 10
Auto changeover only (Auto) **See page 10
13 Adaptive Intelli- 1 On **See page 10
gent Recovery TM O Off
14 Temperature 0 Fahrenheit
display 1 Celsius
15 Compressor 5
protection
16 Schedule format 0
1
Five-minute compressor off time **See page 10
[Other options: 0, 1, 2, 3 or 4-minute off time]
5/2 (programmable weekdays and weekends)
5/1/1 (weekdays, Saturday & Sunday programmable)