Installation Guide
[f you have di[Yiculty with your thermostat, please try the suggestions below. Most
problems can be corrected quickly and easily:
Display is blank * Check circuit breaker and reset if necessary.
. Make sure power switch at heating & cooling system is on.
Make sure furnace door is closed securely.
if thermostat is battery powered, make sure fresh AA alkaline batteries
are correctly installed (see page 7).
Temperature
se_ings de not
change
Make sure heating and cooling temperatures are set to acceptable ranges:
Heat: 40° to 90°F (4.5 ° to 32°C).
. Cool: 50 ° to 99°F (10 ° to 37°C).
Heating system
does not respond
("Heat On"
appears on
SCan)
Cooling system
does not respond
("Cool On"
appears on
SCan)
Fan does not
turn on in a car
for heat
Heat pump
issues coel air
in heat mode_
Or warm air in
cool mode
HeatJcool both
On at same time_
or heat does
not turn off
o Check for 24 Vac at the equipment on the secondary side of the trans-
former between power and common, if voltage is not present, check the
heating equipment to find the cause of the problem.
Check for 24 Vac between the heat terminal (VV)and the transformer
common, if 24 Vac is present, the thermostat is functional. Check the
heating equipment to find the cause of the problem.
o Check for loose or broken wires between the thermostat and the heating
equipment.
o Check for 24 Vac at the equipment on the secondary side of the trans-
former between power and common, if voltage is not present, check the
cooling equipment to find the cause of the problem
Check for 24 Vac between the cooling terminal (Y) and the transformer
common, if 24 Vac is present, the thermostat is functional. Check the
cooling system to find the cause of the problem.
Check for loose or broken wires between the thermostat and the cooling
equipment.
Check Installer Setup, Function 3 (Fan Control), to make sure the fan
control is properly set to match the type of system (see page 8).
* Check Installer Setup, Function 2 (Changeover Valve), to make sure it is
properly configured for your system (see page 8).
Check Installer Setup, Function 1 (System Type), to make sure it is set to
match the installed heating/cooling equipment (see page 8).
* Check to make sure heating and cooling wires are not shorted together.