INSTALLATION INSTRUCTIONS
69-0115-11
L4064B, L4064R
Universal Combination Fan and
Limit Controllers
APPLICATION
These combination warm air fan and limit controllers
are suitable for various types of forced air heating
systems. The controllers have 2 switches; one which
opens the limit circuit if the plenum temperature
exceeds the preset safety limit; it resets automatically.
The other switch turns the fan on and off. The fan is
turned on and off according to plenum temperature.
The L4064R has a special high temperature range
suitable for gravity heating systems. All models may
be used as limit controllers by wiring only the limit
side. Limit contacts are suitable for both line voltage
and low voltage. For low voltage applications, the
brass jumper must be removed.
OPERATION
As the plenum temperature rises, the coiled bimetal
sensing element of the control warps and
mechanically makes the fan contacts (at the FAN ON
temperature setting). During normal operation, the
call for heat ends before the LIMIT setting is reached
and the fan contacts break as the plenum
temperature falls and the FAN OFF setting is reached.
If the call for heat continues until the temperature in
the plenum rises to the LIMIT setting, the bimetal
element will mechanically break the limit contacts
and de-energize the heating control circuit.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to fol-
low them could damage the product or cause a
hazardous condition.
2. Check the ratings given in the instructions and
on the product to make sure the product is suit-
able for your application.
3. Installer must be a trained, experienced service
technician.
4. For 230 VAC application, use of double insu-
lated cable is required.
5. After installation is complete, check out product
operation as provided in these instructions.
WARNING
If limit switch is used on a low voltage
circuit, failure to remove brass jumper can
cause electrical shock hazard and/or
damage to low voltage controls.
CAUTION
1. Disconnect power supply before connecting
wiring to prevent electrical shock or equipment
damage.
2. When connecting cable or conduit to control,
avoid straining the control case.
Follow furnace or burner manufacturer’s instructions,
if available. Maximum element temperature is:
L4064B—350 ºF (177 ºC).
L4064R—250 ºF (121 ºC) above limit setting.
Maximum switch temperature is:
L4064B,R—190 ºF (88 ºC).
Question and Answer IconNeed help?

Do you have a question about the Honeywell L4064B and is the answer not in the manual?

Honeywell L4064B Specifications

General IconGeneral
Switching ActionSPDT
DifferentialAdjustable
MaterialMetal
Electrical ConnectionsScrew terminals
TypeFan and limit control
Voltage Rating120 Vac, 240 Vac
ApprovalsUL listed
Sensing ElementBimetal

Summary

Application

Operation

Installation Instructions

Installation Steps

Follow these instructions carefully for safe and correct product installation.

Low Voltage Circuit Warning

Caution about removing brass jumper for low voltage circuits to prevent shock or damage.

General Installation Precautions

Disconnect power, avoid straining case, and follow manufacturer instructions.

Location Considerations

Surface Mounting

Swivel Mounting

Wiring Instructions

Brass Jumper Removal

Instructions on removing the brass jumper for low voltage circuits.

Wiring Connections Overview

Guidelines for connecting wires using push-in terminals or female receptacles.

Standard Wire Push-in Terminals

Specific steps for connecting wires to standard push-in terminals.

Female Receptacle Wiring

Instructions for connecting wires using female receptacles for accessory equipment.

Checkout Procedure

Fan Setting Adjustment

Manual Fan Switch Operation

Limit Setting Adjustment

Related product manuals