EN2C-0112SZ20 R0202 4
Technical Data
Housing
impact-proof, heat-resistant synthetic material
Colour: black
Drive motor
reversible synchronous motor
Switch point setting
stepless cam setting, lever-operated or spindle-driven
cams;
if spindle-driven, with superimposed scale
Position indicator
scale
Connection system
terminal blocks
Gearing
spur gearing, maintenance-free
Drive shaft
steel
Fitting and fastening
Fastened from inside via tapped M 5 through-holes
Diagram Shaft Drive Load torque Holding Voltage Type Remarks
time torque
Nr. Nr. s Nm Nm V
S1 5 5 2,5 0,8 230 LKS 160-02 B 5-5 S1 standard version
S2 5 5 2,5 0,8 230 LKS 160-04 B 5-5 S2 standard version
S1 5 3 1,5 0,6 230 LKS 160-08 B 5-3 S2
S1 5 5 2,5 0,8 230 LKS 160-10 B 5-5 S1
S2 5 3 1,5 0,6 230 LKS 160-12 B 5-3 S2
S6 5 34 3 3 230 LKS 160-18 B 5-5 S2
S2.1 5 5 2,5 0,8 230 LKS 160-19 B 5-5 S2.1 Shaft with adapter
S3.2 5 5 2,5 0,8 110 LKS 160-28 B 5-5 S3.2
S4 5 5 2,5 0,8 230 LKS 160-36 B 5-5 S4
S13 6 34 3 3 230 LKS 160-43 B 6-34 S13 Spindle-driven cam
S2 5 12 3 1,5 230 LKS 160-50 B 5-12 S2
S4 5 5 2,5 0,8 230 LKS 160-51 B 5-5 S4
S2 5 8 3 1,5 230 LKS 160-52 B 5-8 S2 Other cam colours
S8.P1 5 12 3 1,5 230 LKS 160-57 B 5-12 S8.P1 Potentiometer can be retrofitted
S4 5 12 3 1,5 230 LKS 160-60 B 5-12 S4
S6 5 5 2,5 0,8 230 LKS 160-61 B 5-5 S6
S8.P1.1 5 34 3 3 230 LKS 160-69 B 5-34 S8.P1.1
S6.1 5 5 2,5 0,8 110 LKS 160-71 B 5-5 S6.1
S4.9 5 5 2,5 0,8 230 LKS 160-74 B 5-5 S4.9 Relays control 24 VDC
S6.2 5 65 3 3 230 LKS 160-76 B 5-65 S6.2
S8.P1 5 5 2,5 0,8 230 LKS 160-77 B 5-5 S8.P1 Potentiometer can be retrofitted
S12 5 30 3 3 230 LKS 160-78 B 5-30 S10 Face down
counter-clockwise rotation
3)
4)
6)
5)
2)
1)
7)
Legend
1) when viewing from direction A (see dimensional drawing)
2) see “Circuit diagrams”
3) see “Dimensional drawing”
4) at 50 Hz for 90°
at 60 Hz, Drive times are about 20 % shorter
5) under nominal conditions
under extreme conditions (e.g. +60 °C, 230V -15%) the torques will be 25% lower
6) +10% -15%; 50...60Hz
at -15%; torque reduced by approx. 20% at undervoltage
7) Standard: Lever-operated cam
PCBs
for all electrical functions, increased conductor thickness
Mains voltage
230 V -15% +10% or
110 V -15% +10%
Mains frequency
50 Hz or 60 Hz
Safety class
II VDE 0631
Power consumption
approx. 4 VA
Duty cicle
depending on motor, 50 to 70 % in 2 minutes
Interference suppression
N (according to VDE 0785)
Actuating angle
max. 90°
Mounting position
any