EasyManua.ls Logo

Honeywell MiniPlus FF06 User Manual

Honeywell MiniPlus FF06
30 pages
Go to English
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
MiniPlus FF06 / FF06-AAM
Einbauanleitung Installation instructions Notice de montage
Installatiehandleiding Istruzioni di montaggio Instrucciones de montaje
Beépítési útmutató Instrucţiunile de montaj
Инструкции по установке
Anleitung zum späteren Gebrauch aufbewahren!
Keep instructions for later use!
Conserver la notice pour usage ultérieur!
Handleiding bewaren voor later gebruik!
Conservare le istruzioni per uso successivo!
Guardar estas Instrucciones para su uso futuro!
Az útmutatót őrizze meg a későbbi használatra!
Pstraci instrucciunile pentru o utilizare ulterioar!
Сохранить инструкцию для последующего
пользования!
Feinfilter
Fine filter
Filtre fin
Fijnfilter
Filtro a maglia fine
Filtro fino
Ivóvíz finomszűrő
Filtru fin
Фильтр тонкой очистки для питьевой
воды
EBA-FF06-FF06AAM Rev. A
Question and Answer IconNeed help?

Do you have a question about the Honeywell MiniPlus FF06 and is the answer not in the manual?

Honeywell MiniPlus FF06 Specifications

General IconGeneral
BrandHoneywell
Maximum Operating Pressure16 bar
ModelFF06
ApplicationResidential water filtration
Connection Size1/2", 3/4", 1"
Operating pressure1.5 - 16 bar
Operating temperature5 - 30 °C
Mesh Size100 micron
Filter LifeReplaceable Filter Element
Maximum Operating Temperature30 °C
Inlet/Outlet Size1/2", 3/4", 1"
Weight0.4 kg

Summary

Safety Guidelines

Technical Data

Assembly

Installation Guidelines

Install in horizontal pipework with filter bowl downwards. Ensure good access. Protect against frost. Fit after water meter.

Assembly Instructions

Recommend inlet check valve. Observe flow direction. Do not solder sockets with filter. Flush pipework. Install filter without tension.

Drain for Rinse Water

Rinse water must be piped to the drain without back pressure. Discharge into drain connector or floor drain.

Maintenance

Inspection and Rinse Filter

Inspect and rinse filter every 2 months. Non-compliance can cause blockage and pressure drop. Red coating is normal.

Replace Filter Mesh

Steps to replace filter mesh: close valves, release pressure, unscrew bowl, remove cartridge, replace mesh, reassemble.

Cleaning

Clean filter bowl and filter every 2 months. Do not use solvents. Observe detergent disposal rules.