GUIDE SPECIFICATION
63-2676-03
TB7100A1000 MultiPRO™
Multispeed and Multipurpose Thermostat
FOR CONVENTIONAL, HEAT PUMP, FAN COIL AND PTAC SYSTEMS
GENERAL
A. OVERVIEW: The contractor shall furnish, install, and place in operating condition an HVAC control system
described herein. All units shall be located in accordance with the plans.
B. TYPE OF SYSTEM: System Requirements:
a. Control up to 1 heating and 1 cooling stage for gas heat, electric heat or conventional
rooftops. Up to 2 heat and 1 cool for heat pump, fan coil (2 or 4 pipe), and PTAC.
b. Up to 3 fan speeds for fan coil and 2 fan speeds for PTAC applications
c. Remote setback capability for occupancy sensors and timeclocks (optional)
d. Changeover input for 2 pipe fan coil systems.
e. Fan ramping and fan reset algorithms for fan coil and PTAC applications.
f. Provide minimum 2 year clock backup.
g. Provide two Occupied and two Unoccupied periods per day.
h. Offer automatic heat/cool changeover with 2°F minimum deadband.
i. Provide cumulative override capability for a 1 to 12 hour installer-adjustable period.
j. Include a comfort adjust feature to modify setpoints for the override duration.
k. Provide Proportional plus Integral (P + I) temperature control.
l. Display room temperature in °F or °C.
m. Use multiple remote sensors (optional).
n. Provide five levels of keypad lockout - none, schedule / system, schedule / system /
fan, schedule / system / fan / setpoint, and complete.
o. Provide Holiday Override, 1-365 days.
p. Provide separate configurable recovery ramps for heating and cooling.
q. Provide separate configurable cycle rates for heating and cooling response.
r. Programmable or non-programmable modes.
System Components:
a. Seven day programmable thermostat with subbase.
b. Wall mount temperature sensors (optional).
C. CODES AND
STANDARDS:
The system shall comply with applicable provisions of ASHRAE 90-75.
These specifications are based on equipment from Honeywell to set a standard for design and
quality.
D. WIRING: All wiring shall meet National Electrical Codes and local electrical codes.
E. TESTING
GUARANTEE
SERVICE:
Prior to installation, the contractor shall provide copies of submittals.
The contractor is responsible for assuring that conduit and wire quantity, size, and type are
suitable for the equipment supplied.
Upon completion, the contractor shall conduct a total system test for the owner and
engineer.
All components, parts, and assemblies supplied by the manufacturer shall be guaranteed
against defects in materials and workmanship for 2 years.
Warranty service shall be performed by the contractor.